Vermont Casting AIR TIGHT WOOD STOVE Stove User Manual


 
6
Floor Protector
Installation on a Concrete Floor
An appliance mounted on a concrete floor does not require floor protection.
Carpeting and any other combustible material shall not cover the Floor Protector.
If a combustible surface is applied to the concrete floor, a clearance must be maintained equivalent to the
area reserved for the floor protector. See diagram below.
Installation on a Combustible Floor
If the appliance is to be installed on a combustible floor or a combustible floor covering, it must be installed
on a 3/8”(10mm) thick non-combustible millboard floor protector or durable equivalent. The pad must be
installed beneath the appliance extending 18”(457mm)in Canada, 16”(406mm) in the U.S. on any side
equipped with a door, and 8”(203mm) on all other sides. In the U.S. the pad must cover any horizontal
chimney connector runs and extend 2”(51mm) beyond each side.
A grouted ceramic floor-tile surface installed per local building code is considered a durable equivalent.
Wall Line
Chimney Connector
Floor Protector
Door Side of
Appliance
2” (51mm) 2” (51mm)
8” (203mm)
8” (203mm)
8” (203mm)
*18” (457mm)
**16” (406mm)
* CANADA
** UNITED STATES