Vermont Castings Pinnacle & Stardance Direct Vent - Rear Vent Gas Heaters
20003457
Vent Termination Clearances
Your stove is approved to be vented either through the
side wall, or vertical through the roof.
Vermont Castings, Majestic Products does not
require any opening for inspection of vent pipe.
Only Vermont Castings, Majestic Products vent-
ing components specifically approved and
labelled for this stove may be used.
Minimum clearances between vent pipes and
combustible materials is one (1") inch (25 mm),
except where stated otherwise.
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24" from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent
termination area after snow falls, and clear to prevent
accidental blockage of venting system. When using
snow blowers, make sure snow is not directed towards
vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown in Figure 9.