Carrier PSV Heat Pump User Manual


 
63
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
LEGEND
SCREEN NAME POINT NAME
PASSWORD
LEVEL
EDITABLE RANGE DEFAULT NOTES
Configuration
Alarm
Configuration
SPT Occupied Alarm
Hysteresis
Admin Password
level access only
X2 - 20 F5 F
Defines the hysteresis applied above
the cooling and below the heating set
points before an alarm condition will
occur
SPT Alarm Delay X 0 - 30 min per degree 10 min
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
SPT Unoccupied Low
Alarm Temperature
X 35 - 90 F 45 F
Defines the fixed unoccupied
ow SPT alarm limit
SPT Unoccupied High
Alarm Temperature
X 45 - 100 F 95 F
Defines the fixed unoccupied
high SPT alarm limit
SAT Low SAT
Alarm Limit
X 15 - 90 F 45 F
Defines the fixed minimum
SAT alarm limit
SAT High SAT
Alarm Limit
X 90 - 175 F 120 F
Defines the fixed maximum
SAT alarm limit
Condensate Overflow
Alarm Delay
X 5 - 600 sec 10 sec
Defines the delay time before an alarm
is generated after the alarm condition
occurs
Space Humidity Occupied
High Alarm Limit
X 45% - 100% 100%
Defines the fixed occupied
high space RH alarm limit
Space Humidity Alarm
Delay
X 0 - 30 min per % RH 5 min
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Space Humidity Unoccu-
pied High Alarm Limit
X 45% - 100% 100%
Defines the fixed unnoccupied
high space RH alarm limit
IAQ/Ventilation Occupied
High Alarm Limit
X 0 - 9999 ppm 1100 ppm
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
IAQ/Ventilation
Alarm Delay
X 0.1 - 1.0 min per ppm 0.25 min
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Rnet Sensor SPT Alarm X Ignore/Display Ignore
Determines if the SPT alarm is
displayed on the local Rnet sensor
Rnet Sensor SAT Alarm X Ignore/Display Ignore
Determines if the SAT alarm is
displayed on the local Rnet sensor
Rnet Sensor Compressor
Lockout Alarm
X Ignore/Display Display
Determines if the Compressor Lockout
alarm is displayed on the local Rnet
sensor
Rnet Sensor Condenser
Water Temperature Alarm
X Ignore/Display Display
Determines if the Condenser Water
Temperature alarm is displayed on the
local Rnet sensor
Rnet Sensor Condensate
Overflow Alarm
X Ignore/Display Display
Determines if the Condensate
Overflow alarm is displayed on the
local Rnet sensor
Rnet Sensor Dirty
Filter Alarm
X Ignore/Display Display
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Rnet Sensor Space
High Humidity Alarm
X Ignore/Display Ignore
Determines if the High Space
RH alarm is displayed on the
local Rnet sensor
Configuration
Linkage
Loop Control Network
Number
See TPI
Loop Control Network
Address
See TPI
Number of Linked Heat
Pumps
See TPI
°°
°°
°°
°°
°°
BAS Building Automation System
DCV Demand Controlled Ventilation
IAQ Indoor Air Quality
OAT Outdoor Air Temperature
RH Relative Humidity
SAT Supply Air Temperature
SPT Space Temperature
TPI Third Party Integration