Carrier GT-PX Heat Pump User Manual


 
Indoor & Outdoor Split
Geothermal Comfort Systems
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
31
50YCS042 / 38WQS042 With GAH042
Performance capacities shown in thousands of Btuh.
WPD HEATING - EAT 70°F COOLING - EAT 80/67 °F
EWT °FGPM
PSI FT
CFM
HC KW HE LAT COP HWC TC SC KW HR EER HWC
5.2 2.0 4.7 1150
1400 Operation not recommended
20 9.0 4.9 11.2 1150 Operation not recommended
1400
10.5 6.2 14.3 1150 26.5 2.62 17.5 91.3 2.96 3.6
1400 27.2 2.60 18.4 88.0 3.07 3.1
5.2 2.0 4.6 1150 31.3 2.71 22.0 95.2 3.38 4.1 50.5 33.1 1.67 56.2 30.3 1.6
1400 31.3 2.65 22.3 90.7 3.46 3.5 52.4 36.4 1.73 58.3 30.3 1.3
30 9.0 4.7 10.9 1150 31.4 2.71 22.2 95.3 3.40 4.3 49.9 32.6 1.62 55.4 30.9 1.6
1400 31.9 2.67 22.8 91.1 3.51 3.6 52.5 36.6 1.68 58.2 31.3 1.4
10.5 6.0 13.9 1150 31.6 2.71 22.4 95.4 3.42 4.4 49.3 32.2 1.57 54.6 31.4 1.7
1400 32.5 2.68 23.3 91.5 3.55 3.8 52.6 36.9 1.63 58.2 32.4 1.5
5.2 1.9 4.5 1150 35.8 2.80 26.3 98.9 3.75 4.8 48.6 32.2 1.94 55.2 25.1 2.7
1400 35.9 2.73 26.6 93.7 3.85 4.2 50.4 35.4 2.01 57.2 25.1 2.5
40 9.0 4.6 10.6 1150 36.1 2.81 26.5 99.1 3.76 5.0 48.0 31.7 1.87 54.4 25.6 2.5
1400 36.9 2.77 27.4 94.4 3.90 4.3 50.5 35.6 1.94 57.1 26.0 2.4
10.5 5.8 13.5 1150 36.3 2.82 26.7 99.3 3.77 5.2 47.3 31.3 1.81 53.5 26.1 2.3
1400 37.8 2.80 28.3 95.0 3.96 4.5 50.5 35.9 1.88 57.0 26.9 2.3
5.2 1.9 4.3 1150 40.4 2.88 30.6 102.5 4.11 5.6 46.7 31.3 2.21 54.2 21.1 3.8
1400 40.4 2.82 30.8 96.7 4.21 4.8 48.4 34.3 2.29 56.2 21.1 3.6
50 9.0 4.4 10.2 1150 40.7 2.91 30.8 102.8 4.10 5.8 46.0 30.8 2.13 53.3 21.6 3.4
1400 41.8 2.87 32.0 97.7 4.27 5.0 48.4 34.6 2.21 56.0 21.9 3.4
10.5 5.6 13.0 1150 41.1 2.94 31.1 103.1 4.10 6.0 45.4 30.4 2.05 52.4 22.1 2.9
1400 43.2 2.92 33.2 98.6 4.34 5.2 48.5 34.9 2.13 55.8 22.8 3.1
5.2 1.8 4.2 1150 44.5 2.98 34.3 105.8 4.37 6.3 45.3 31.0 2.44 53.6 18.6 4.6
1400 45.0 2.90 35.1 99.7 4.55 5.5 46.9 33.3 2.52 55.5 18.6 4.6
60 9.0 4.3 9.9 1150 45.2 3.02 34.9 106.4 4.38 6.5 45.4 30.4 2.36 53.4 19.3 4.2
1400 46.4 2.94 36.3 100.7 4.61 5.7 47.0 33.7 2.42 55.2 19.4 4.2
10.5 5.5 12.6 1150 45.9 3.06 35.4 106.9 4.40 6.7 45.5 29.9 2.27 53.2 20.0 3.8
1400 47.8 2.99 37.6 101.6 4.68 5.9 47.0 34.1 2.31 54.9 20.3 3.9
5.2 1.8 4.0 1150 48.6 3.08 38.1 109.1 4.62 7.0 43.9 30.8 2.67 53.0 16.4 5.5
1400 49.5 2.98 39.4 102.8 4.87 6.2 45.5 32.3 2.75 54.8 16.5 5.5
70 9.0 4.1 9.6 1150 49.6 3.13 38.9 109.9 4.65 7.3 44.7 30.0 2.58 53.5 17.3 5.0
1400 50.9 3.02 40.6 103.7 4.94 6.4 45.5 32.7 2.63 54.4 17.3 5.1
10.5 5.3 12.2 1150 50.6 3.17 39.8 110.8 4.67 7.5 45.5 29.3 2.49 54.0 18.2 4.6
1400 52.3 3.07 41.9 104.6 5.00 6.6 45.5 33.2 2.50 54.0 18.2 4.8
5.2 1.7 3.9 1150 53.0 3.16 42.2 112.7 4.91 7.9 41.7 29.8 2.97 51.8 14.0 6.3
1400 54.1 3.06 43.6 105.8 5.17 6.7 43.2 31.2 3.06 53.6 14.1 6.4
80 9.0 4.0 9.3 1150 54.3 3.23 43.2 113.7 4.92 8.1 42.5 29.1 2.87 52.3 14.8 5.8
1400 55.7 3.13 45.1 106.9 5.22 7.0 43.2 31.7 2.92 53.2 14.8 6.0
10.5 5.1 11.8 1150 55.5 3.30 44.2 114.7 4.93 8.4 43.2 28.4 2.77 52.7 15.6 5.4
1400 57.4 3.19 46.5 108.0 5.27 7.3 43.2 32.2 2.78 52.7 15.6 5.6
5.2 1.6 3.8 1150 57.5 3.25 46.4 116.3 5.19 8.7 39.5 28.8 3.27 50.7 12.1 7.1
1400 58.6 3.15 47.9 108.8 5.46 7.3 40.9 30.2 3.37 52.4 12.1 7.4
90 9.0 3.9 8.9 1150 58.9 3.34 47.5 117.5 5.17 9.0 40.2 28.1 3.16 51.0 12.7 6.7
1400 60.5 3.23 49.5 110.0 5.49 7.7 40.9 30.7 3.21 51.9 12.7 6.9
10.5 4.9 11.4 1150 60.4 3.43 48.7 118.6 5.16 9.4 41.0 27.4 3.05 51.4 13.4 6.3
1400 62.5 3.31 51.2 111.3 5.53 8.0 40.9 31.1 3.06 51.4 13.4 6.4
5.2 1.6 3.6 1150 37.5 28.2 3.65 50.0 10.3 8.0
1400 38.9 29.6 3.76 51.7 10.3 8.3
100 9.0 3.7 8.6 1150 38.2 27.6 3.53 50.3 10.8 7.5
1400 38.9 30.0 3.59 51.1 10.8 7.8
10.5 4.7 11.0 1150 38.9 26.9 3.41 50.6 11.4 7.1
1400 Operation not recommended 38.9 30.5 3.42 50.6 11.4 7.2
5.2 1.5 3.5 1150 35.6 27.6 4.04 49.4 8.8 8.9
1400 36.8 29.0 4.16 51.0 8.8 9.2
110 9.0 3.6 8.3 1150 36.2 27.0 3.91 49.6 9.3 8.4
1400 36.8 29.4 3.97 50.4 9.3 8.6
10.5 4.6 10.5 1150 36.9 26.3 3.77 49.7 9.8 7.9
1400 36.9 29.9 3.78 49.8 9.8 8.1
Rev: 12/12/03 BInterpolation is permissable, extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.