Carrier 53DFS250-FS Thermostat User Manual


 
L'Yl_ I[,."15"1!1_
(_ Adjust the minimum
allowable cool set point
when security is in effect.
(Step 10 only appears
if Step 8 is not 0.)
(35 to 99 F)
LU
_) C
Select thermostat
operation in degrees
j) Fahrenheit orCentigrade.
F
F
On
(_ Select the display back-
light always On, or Off
after 8 seconds.
off
ON
_'nR
U,UU
(_ Adjust the preoccupancy
_j) O:O0= off
Select the unit ID for
'Soft Start'. This is used
in multiple installs to
stagger equipment turn I_
on times. 0 = off.
Each increment = 30 second delay.
(0 to 99) P.dl_l
Select the sensor type:
Yes = Outside or Duct
sensor
No =Automatic DetectionofRemote Sensor
No
To view Outside or Duct temperature
press and hold Mode 2 seconds, rain.
The thermostat will not control to Outside or Duct Sensors.
Outsi@
Press
MODE O
OVERRIDE O
Press the Mode button, While holding the Mode,
press the Override button leave the Setup screens.
ff no buttons are pressed, the display will leave the
set screens after 30 seconds.
STEP NO,
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Advanced Setup Table
DESCRIPTION RANGE FACTORY
DEFAULT
Time of day clock set 24 hour 12:00 Am
Day of the week Su - Sa Mo
Fan Mode Auto / d| Auto
Heat Pump On or Off Off/On Off
Deadband or Temperature swing 1 - 6 2
Forced minimum difference 0 - 6 2
heat/coot
Cycles per hour d, dl, 2 - 6 6
Security Levets 0- 3 0
Maximum allowable Heat set point 35- 99 F 80 F
Minimum allowable Coot set point 35 - 99 F 65 F
Fahrenheit or Centrigrade F / C F
Thermogtow TM Backlight Off / On On
Fan Purge timer 0:00 - 3:00 0:00
Soft Start 0 - 99 0
Remote Sensor Yes / No No
CLOCK BACKUP -- In the event of a power loss,
the thermostat internal clock will continue to keep
proper time for a minimum of 48 hours without
external power or batteries.
MINIMUM HEAT/COOL SET POINT DIFFERENCE
-- The Heat and Cool set points will not be allowed
to come any closer to each other than the value set
in Advanced Setup Step 6, on page 4. This mini-
mum difference is enforced during Auto changeover
and Program On operation.
ENERGY SAVING SMART FAN -- If Fan On is
selected, the fan will run continuously at all times. If
fan is in Off Mode it will only run if there is a heating
or cooling demand during programmed unoccupied
periods.
OVERRIDE -- As explained on page 2, pressing
the Override button during a programmed, Unoccu-
pied period will force the thermostat into Occupied
1, temporarily, up to 4 hours. If the Override button
is pressed during an Occupied period, the thermo-
stat will be forced into Unoccupied and the occu-
pied period (1,2 or 3), it was forced out of will be
turned off, only for that day.
During Override periods the set points may be
adjusted, but they will not be remembered after
Override ends.
FAN PURGE TIMER -- When this feature is acti-
vated, the fan will turn on during Unoccupied at a
preset amount of time prior to Occupied 1. This pre-
occupancy fan purge timer may be set as instructed
on this page, Step 13,from 0 to 3 hours. 0 = this
feature turned off.
KEYPAD LOCK -- To prevent unauthorized use of
the thermostat, the front panel buttons may be dis-
abled. To disable, or 'lock' the keypad, press and
hold the Mode button. While holding the Mode but-
ton, simultaneously press the Up and Down but-
tons. Locked will appear on the display.
Press all 3 for _) Locked
Keypad Lockout _ "--_
To unlockthe buttons, again press and hold the
Mode button. While holding the Mode button, simul-
taneously press the Up and Down buttons. Locked
will disappear from the display.
DRY CONTACT SWITCH -- The terminals are
'normally open'. Closing or completing the circuit
will cause the thermostat to enter Occupied 1. This
feature allows an external device such as a central
time clock, occupancy sensor, or a telephone-
activated device to force one or more thermostats
into Occupied 1. For the Dry Contact to work the
thermostat must be in Program On. Set Occupied
1 to Offforall 7days, so the Contact closure will be
in control. When the thermostat is forced into Occu-
pied 1 via the Dry Contact closure, the icon
Occupied 1 will blink.
CK1
GND