Carrier 42GW Air Conditioner User Manual


 
42 GW
GB - 16
Maintenance and owner's guide
Maintenance
Cleaning and maintenance operations must be carried out by
specially trained personnel.
Before performing any service or maintenance operations,
turn OFF the main power switch.
To open the unit grille:
Turn the two screws through 90° (1/4 turn).
Filter cleaning
Clean filters in accordance with the actual operating
conditions and times (approximately every 6 months).
The acrylic air filter is washable in water.
Electrostatic and active carbon filters (which can be used on
the unit) are not washable but must be replaced.
Extract the filter.
First vacuum clean the filter, then wash under tap water and
finally dry.
Replace the filter in the correct position.
Prolonged shutdown:
Before starting the air conditioner:
- clean or replace the unit air filters.
- check and clean the drain pan and the condensate discharge of
the unit
- check tightness of electric connections.
Additional maintenance
The electric panel is easily accessible by removing the cover
panel.
The inspection or replacement of internal components such as:
fan motor, coil, condensate discharge pump, float switch, electric
heater (if fitted), involve the removal of the condensate drain pan.
Condensate drain pan removal
During the removal operation of the condensate drain pan
protect the floor with a plastic sheet under the unit.
Remove the frame-grille assembly by loosening the screws;
drain the condensate water contained in the drain pan into
a bucket of at least 10 litres capacity, using the special
drain with a rubber plug.
Remove the electrical panel cover and disconnect the electric
connections, connectors C
V, CG, CP and the yellow-green
ground wire (see drawing in electrical connections
section).
Remove the four fixing screws on the side of the drain pan and
carefully remove the condensate drain pan.
Guide for the owner
When installation and tests are completed instruct the Owner on the
main operating modes of the air conditioner, such as:
Turning the unit ON and OFF.
Changing the operation modes.
Temperature selection.
Leave the installation manual with the owner for future use dur-
ing maintenance operations or for any other needs.
Acrylic fibre