Table 1C — 40RMS Physical Data, English
UNIT 40RMS 008 010 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 7
1
⁄
2
8
1
⁄
2
10 12
1
⁄
2
15 20 25 30
OPERATING WEIGHT (lb)
Base Unit 390 391 391 661 677 683 1035 1042
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 3000 3400 4000 5000 6000 8000 10,000 12,000
Airflow Range (cfm) 2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp
(Standard Motor)
208/230-1-60 2.4 2.4 — — — — — —
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
230-3-50 and 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 — — — — — —
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
230-3-50 and 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure
(psig)
435
Face Area (sq ft) — Upper 8.3 9.0 4.9 8.3 8.3 11.0 12.4 15.5
Face Area (sq ft) — Lower — — 4.9 5.5 8.3 8.3 12.4 12.4
Rows...Fins/in. 3...15
STEAM COIL
Max Working Pressure
(psig at 400 F)
175
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure
(in. wg)
150
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft
3
) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...1
3
⁄
8
ODF 1...1
3
⁄
8
ODF 2...1
3
⁄
8
ODF 2...1
3
⁄
8
ODM 2...1
3
⁄
8
ODM 2...1
3
⁄
8
ODM 2...2
1
⁄
8
ODM 2...2
1
⁄
8
ODM
Chilled Water — Out 1...1
3
⁄
8
ODF 1...1
3
⁄
8
ODF 2...1
3
⁄
8
ODF 2...1
3
⁄
8
ODM 2...1
3
⁄
8
ODM 2...1
3
⁄
8
ODM 2...2
1
⁄
8
ODM 2...2
1
⁄
8
ODM
Steam Coil, In (MPT) 1...2
1
⁄
2
1...2
1
⁄
2
Steam Coil, Out (MPT) 1...1
1
⁄
2
1...1
1
⁄
2
Hot Water Coil, In (MPT) 1...1
1
⁄
2
1...1
1
⁄
2
1...2
Hot Water Coil, Out (MPT) 1...1
1
⁄
2
1...1
1
⁄
2
1...2
Condensate (PVC) 1...1
1
⁄
4
ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2
4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Access Location Either Side
4