Table 6 Fan Contactor Coil Data
UNIT
40RM, 40RMQ
40RMS
VOLTAGE
(vac)
MAXIMUM
HOLDING
VA
007-034 24 10
Connecting Ductwork Refer to the Carrier Sys-
tem Design Manual for the recommended design and layout
of ductwork. Figure 15 shows recommended duct connec-
tion to units with 2 fans.
DISCHARGE CONNECTIONS — Duct flanges are factory
supplied; they are shipped inside the unit attached to the hair-
pin end of the coil tube sheet for field installation. Using the
existing screws, install the duct flanges on the unit’s fan deck.
Each fan discharge requires 2 flanges; each flange must be
bent in the middle to conform to the discharge opening. See
Fig. 16. After flanges are installed, connect them to the sup-
ply duct using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to pre-
vent high air friction losses and air noise.
RETURN CONNECTION When using return-air duct-
work, route return-air duct to the unit’s return air inlet near
the filter rack, using a canvas connection to prevent trans-
mission of unit vibration. If the duct blocks off the unit’s
access panel, provide a slip joint in the ductwork to permit
removal for servicing.
OUTDOOR-AIR INLET CONNECTION — Connect outdoor-
air inlet to field-installed accessory economizer. Refer to econo-
mizer Installation Instructions.
Return-Air Filters Type and size of filters are
shown in Tables 1A-1F and are factory-supplied and in-
stalled. In all units with 2 fans, a filter replacement tool (hook)
is shipped inside the unit for field use when replacing filters.
See the Service section for instructions on filter element
replacement.
Fig. 14 Unit Wiring
LEGEND
CB Circuit Breaker
HC Heating Contactor
HTR Electric Heater
IFC Indoor-Fan Contactor
IFM Indoor-Fan Motor
NEC National Electrical Code
TB Terminal Block
T’STAT Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.
Fig. 15 Typical Fan Discharge Connections
for Multiple Fan Units
596 22