Carrier 38HDF018-036 Air Conditioner User Manual


 
9
LEGEND
NOTES:
1. Compressor and fan motors are thermally protected.
2. Wire in accordance with National Electrical Code (NEC) and local codes. Replace
any original wires with 90° C wire or its equivalent.
3. Use minimum 60° C wire for field power wiring.
4. Transformer has internal 4.5A thermal fuse on the primary side.
5. Transformer factory wired for 230 v. For 208 v move black wire to 208 volt tap on
transformer.
6. Crankcase heater and thermostat used on selected models only.
C—Contactor, Compressor
CAP Capacitor
CCHT Crankcase Heater Thermostat
CH Crankcase Heater
COMP — Compressor Motor
EQUIP— Equipment
GND Ground
HPS High-Pressure Switch
LPS Low-Pressure Switch
OFM Outdoor-Fan Motor
OL Overload
TB Terminal Board
TRAN Transformer
Splice (Field)
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Optional or Accessory Wire
Fig. 6 — 38HDF018-036 Typical Wiring Schematic
38HDF OPERATION SEQUENCE
CALL FOR COOLING:
1. Control voltage from transformer to thermostat (24 v).
2. At thermostat 24 v is switched to “G” and “Y.”
3. 24 v from thermostat “G” energizes fan relay at indoor fan coil unit and indoor-fan motor runs.
4. 24 v from thermostat “Y” energizes the contactor coil and the compressor and outdoor-fan motor will both
run.
6. If the internal protection of the compressor or LPS or HPS open, the 24 v to contactor coil will be inter-
rupted. The compressor and outdoor-fan motor will stop.