36
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all
cooling demands.
Default is OF (off).
Option 23 — High Heat Latch Temperature (only available if outdoor
sensor is present)
This selection is only available when Option 1 is set to H2, or h2 and Option 7
(zoning) is set to OF (off). Configuration settings are OF (off), 20, 25, 30, 35, 40,
45, 50, On.
OF (off) —Heating always s tarts in low stage (Y1) and stages up to high stage
(Y1 and Y/Y2) when demand is sufficient a nd staging timer constraints have
been satisfied.
20--50_F/--7--10_C — Outdoor temperature below which both first and second
stages of the compressor are energized to satisfy all heating demands. When a
cycle starts under a high heat latch, it will finish the heating cycle on high stage.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all
heating demands.
Default is OF (off).
Option 24 — Programmable/Non--Programmable (programmable models
only)
This selection allows the installer to configure the Thermidistat Control as either
programmable or non-- programmable. Selections are P, nP.
Default is P.
Option 25 — Number of Programmable Periods (programmable models
only)
This selection allows the installer to c onfigure the Thermidistat Control for two
or four periods per day. Two periods is a common commercial application and