Option 14 — Humidity Display Offset Adjust
The percentage to be added to the displayed humidity to calibrate or deliberately
miscalibrate the measured room humidity (--9% to +9% RH).
Default is 0.
Option 15 — Enable Auto Mode
This selection is not available if the Thermidistat Control is configured as Heat
Only o r Cool Only in Option 1. This allows th e homeowner to select auto
changeover mode in ad dition t o heat and cool. This allows the Thermidistat
Control to automatically change between heating mode and cooling mode when
sufficient demand for heating or cooling exists.
On — Auto mode is available.
OF — Auto mode is not available.
Default is On.
Option 16 — Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the Thermidistat Control
allows the system to operate. Selections are 2, 4, 6.
2 — The heating and cooling outputs will be energized no more than 2 times per
hour. When an output is energized, it will not be energized again for 30 minutes.
4 — The heating and cooling outputs will be energized no more than 4 times per
hour. When an output is energized, it will not be energized again for 15 minutes.
6 — The heating and cooling outputs will be energized no more than 6 times per
hour. When an output is energized, it will not be energized again for 10 minutes.
Default is 4.