Bryant T6--NHP Thermostat User Manual


 
32
4 — Periods WAKE, DAY, EVE, and SLEEP are available.
Default is 4.
Option 26 — Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that
the user is allowed to set. The range is based on the value of the adjustable
deadband Option 11, such that the minimum of the range is 50_Fplusthe
adjustable deadband and the maximum is 90_F.
Default is 52_F (based on the adjustable deadband default = 2).
Option 27 — Maximum Heating Setpoint
This selection allows the installer t o configure the maximum heating setpoint.
The range is based on the adjustable deadband value Option 11, such that the
minimum of the range is 50_F and the maximum is 90_F minus the deadband.
Default is 88_F (based on the adjustable deadband default = 2).
Option 28 — UV Light Reminder
This selection allows the installer to select the number of months after which the
UV Light icon will be displayed to indicate to the homeowner that it is time to
call the dealer to have the UV Lights replaced. Selections available are OF (off),
6, 12, 18, 24, 30, 36, 42, 48.
OF (off) — The UV Light reminder is turned off and will never be displayed.
6-- 48 The number of months after which the UV Light reminder will be
displayed, “CHECK UV LIGHT”.
Default is OF (off).
Option 29 — Humidifier Pad Reminder
This selects the number of months after which the Humid ifier Pad Reminder
icon will be displayed. This is not based on run time.