Bryant T6--NHP Thermostat User Manual


 
28
programmed. Not available with non--programmable thermostats or when
thermostat is configured as non--programmable.
Default is 90.
Option 13 — Room Air Temperature O ffset Adjust
The number of _F to be added to the displayed temperature to calibrate or
deliberately miscalibrate the measured room temperature ( --5 to +5_F).
Default is 0.
Option 15 — Enable Auto Mode
This selection is not available if the thermostat is configured as Heat Only or
Cool Only in Option 1. This a llows the homeowner to select auto changeover
mode in addition to heat and cool. This allows the thermostat to automatically
change between heating mode and cooling mode when sufficient demand for
heating or cooling exists.
On — Auto mode is available.
OF — Auto mode is not available.
Default is On.
Option 16 — Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the thermostat allows the
system to operate. Selections are 2, 4, 6.
2 — The heating and cooling outputs will be energized no more than 2 times per
hour. When an output is energized, it will not be energized again for 30 minutes.
4 — The heating and cooling outputs will be energized no more than 4 times per
hour. When an output is energized, it will not be energized again for 15 minutes.