If the display module doesn’t power up after power is applied, check the Rc/Rh
and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg
and V+. This voltage will be approximately 12--20VDC. If voltage is present,
check the polarity to make sure it is wired correctly. The display will not power
up if polarity is reversed.
Error Codes
-- -- -- If AC/HP Control cannot properly read room temperature, display will
indicate “----” and all outputs (except fan, if on) will turn off. In the case where
the installer has selected to average the local sensor and the remote room sensor,
the AC/HP display will alternate between “----” for the failed sensor and the
temperature sensed by the working sensor every 10 seconds. The control will
operate from the temperature sensed by the working sensor.
E1 -- If the Display Module and the Equipment Control Module cannot
communicate via two-- wire connection, an E1 will be displayed.
E2 --ThereisnoE2errormessage.
E3 -- If AC/HP Control cannot properly read outdoor temperature, and it is
needed for proper operation, display will indicate “----” in the outdoor
temperature location.
E4 -- If AC/HP Control’s internal memory fails, E4 will be displayed. Replace
AC/HP Control.
Table 3 can be used as a troubleshooting tool for determining which outputs will
be active for a particular configuration and each operating mode.