Bryant T6--NAC Thermostat User Manual


 
34
Daylight Savings Time by setting the day of the week by selecting the
appropriate triangle icon next to the days of the week, the month of the year will
be set in the clock hours location (range 1--12) and the week of the month will be
set in the clock minutes location. The week of the month selections will be F, 2,
3, 4, and L for First, 2nd, 3rd, 4th, and Last. So for the first Sunday in April, the
display would show SUN, 4, F. When 2 is displayed, the installer will then
choose the end date for daylight savings time (Fall). To activate the function, the
installer changes the “2” by pressing the up button and “On” is displayed. The
setting shall be left “On” to enable the Daylight Savings Time function.
Default is OF (off).
Option 32 — Furnace Heat Staging Control (available only when the HP
thermostat is configured to operate AC equipment).
1 Thermostat controls W1 output only and furnace controls the turn on and
turnoffofhigherstagesofheat.
2 — Thermostat will control the W1 and O/W2/B outputs.
Default is 1.
Option 33 — Single or Two --Piece Installation
This configuration allows the thermostat to compensate for the amount of heat
generated by the thermostat electronics to allow more accurate sensing of t he
temperature sensor. The amount of heat compensation will be different between
single installation and two--piece installation.
Range: 1P or 2P
1P — The installation is single piece.
2P — The installation is two separate pieces.
Default is 2P.