Bryant 583B Fan User Manual


 
21
452=5v
457=7v
455=2v
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA
Rated
Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457
(BC) 464
(AC) 457
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
®
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.
If power distribution voltage to unit varies from rated heater voltage,
heater KW will vary accordingly.
C99024
ELECTRICAL DATA
583B (STANDARD) ELECTRICAL DATA
583B WITH ICM FIOP ELECTRICAL DATA
UNIT
SIZE
583B
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR FAN
MOTOR
INDOOR FAN
MOTOR POWER SUPPLY
Min Max RLA LRA FLA FLA MCA
MAX FUSE
OR BKR
024 208/230-1-60 187 253 13.5 61.0 0.8 2.0 19.7 30
030
208/230-1-60 187 253 14.7 73.0 0.8 2.1 21.3 35
208/230-3-60 187 253 9.6 63.0 0.8 2.1 14.9 20
036
208/230-1-60 187 253 15.4 83.0 0.8 3.6 23.7 35
208/230-3-60 187 253 12.2 77.0 0.8 3.6 19.7 30
460-3-60 414 506 5.1 35.0 0.8 1.9 9.1 15
042
208/230-1-60 187 253 18.6 105.0 0.9 4.1 28.3 45
208/230-3-60 187 253 13.8 88.0 0.9 4.1 22.3 35
460-3-60 414 506 6.3 39.0 0.9 2.0 10.8 15
048
208/230-1-60 187 253 20.5 109.0 1.6 4.1 31.3 50
208/230-3-60 187 253 14.7 91.0 1.6 4.1 24.1 35
460-3-60 414 506 6.5 46.0 0.9 2.0 11.0 15
060
208/230-1-60 187 253 27.6 158.0 1.6 6.2 42.3 60
208/230-3-60 187 253 18.1 137.0 1.6 6.2 30.4 45
460-3-60 414 506 9.0 62.0 0.9 3.2 15.4 20
UNIT SIZE
583B
V-PH-HZ
VOLTAGE RANGE COMPRESSOR
OUTDOOR FAN
MOTOR
INDOOR
FAN
MOTOR
POWER SUPPLY
MIN MAX RLA LRA FLA FLA MCA
MAX FUSE OR
CKT. BKR.
024 208/230160 187 253 13.5 61.0 0.9 4.3 22.1 35
030 208/230160 187 253 14.7 73.0 0.9 4.3 23.6 35
036 208/230160 187 253 15.4 83.0 0.9 6.8 27.0 40
042 208/230160 187 253 18.6 105.0 0.9 6.8 31.7 45
048 208/230160 187 253 20.5 109.0 1.6 6.8 34.0 50
060 208/230160 187 253 27.6 158.0 1.6 9.2 45.2 60