Bryant 549B Heat Pump User Manual


 
118
GUIDE SPECIFICATIONS 542J150,180 UNITS
PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP CON-
STANT VOLUME APPLICATION
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 12 to 15 TONS, NOMINAL (COOLING)
136,000 to 172,000 BTUH, NOMINAL
(INPUT HEATING)
BRYANT MODEL NUMBER: 542J
PART 1 GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor rooftop mounted, electrically controlled air-to-air
heat pump unit utilizing reciprocating, semi-hermetic com-
pressor(s) for cooling duty and electric resistance coils for
heating duty. Unit shall discharge supply air vertically or
horizontally (with horizontal supply/return adapter assem-
bly or roof curb) as shown on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard 340.
Designed in accordance with UL Standard 1995.
B. Unit shall be designed to conform to ASHRAE 15, latest
revision.
C. Unit shall be UL-tested and certified in accordance
with ANSI Z21.47 Standards and UL-listed and certified
under Canadian standards as a total package for safety
requirements.
D. Roof curb shall be designed to conform to NRCA
Standards.
E. Insulation and adhesive shall meet NFPA 90A require-
ments for flame spread and smoke generation.
F. Unit casing shall be capable of withstanding 500-hour salt
spray exposure per ASTM B117 (scribed specimen).
G. Unit shall be designed in accordance with ISO 9001, and
shall be manufactured in a facility registered to ISO 9002/
BS5750, Part 2.
H. Each unit shall be subjected to a completely automated
run testing on the assembly line. Units contain a factory-
supplied printout indicating tested pressures, amperages,
data, and inspectors; providing certification of the unit
status at the time of manufacture.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturers
recommendations.
PART 2 PRODUCTS
2.01 EQUIPMENT (STANDARD)
A. General:
Factory assembled, single-piece heat pump unit. Con-
tained within the unit enclosure shall be all factory wiring,
piping, controls, refrigerant charge (R-22), and special
features required prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
and shall be bonderized and coated with a pre-
painted baked enamel finish on all externally
exposed surfaces.
2. Indoor fan compartment interior cabinet surfaces
shall be insulated with a minimum
1
/
2
-in. thick, 1 lb.
density, flexible fiberglass insulation, neoprene
coated on the air side.
3. Cabinet panels shall be easily removable for
servicing.
4. Holes shall be provided in the base rails for rigging
shackles to facilitate maneuvering and overhead
rigging.
5. Unit shall have a factory-installed, sloped conden-
sate drain pan made of a non-corrosive material, pro-
viding a minimum
3
/
4
-in. 14 NPT connection with both
vertical and horizontal drains, and shall comply with
ASHRAE Standard 62.
6. Unit shall have a factory-installed filter access panel
to provide filter access with tool-less removal.
7. Unit shall have standard thru-the-bottom power con-
nection capability (accessory kit is required).
C. Fans:
1. Indoor Fan:
a. Fan shall be belt driven with an adjustable-pitch
motor pulley. The standard fan drive shall have a
factory-installed low-medium static pressure fan
drive. The alternate fan drive option shall have a
factory-installed high static pressure fan drive.
b. Fan wheel shall be double-inlet type with forward-
curved blades.
c. Bearings shall be sealed, permanently lubricated
ball-bearing type for longer life and lower
maintenance.
d. Bearings shall be pillow block type (180 only).
2. Indoor fan shall be made from steel with a corrosion-
resistant finish and shall be dynamically balanced.
3. Outdoor fan shall be of the direct-driven (with totally
enclosed motors) propeller type and shall discharge
air vertically.
4. Outdoor fan shall have aluminum blades riveted to
corrosion-resistant steel spiders and shall be dynam-
ically balanced.
D. Compressor(s):
1. Reciprocating semi-hermetic compressors with
factory-installed crankcase heaters.
2. Factory mounted on rubber grommets and internally
spring mounted for vibration isolation.
3. On independent circuits (180).
4. The size 150 unit semi-hermetic compressor shall be
equipped with an electric unloader for capacity
control.
E. Coils:
1. Standard indoor and outdoor coils shall have copper
or aluminum plate fins mechanically bonded to
seamless internally grooved copper tubes with all
joints brazed.
2. Coils:
a. Copper-fin coils shall be constructed of copper
fins mechanically bonded to copper tubes and
copper tube sheets. Galvanized steel tube sheets
shall not be acceptable. A polymer strip shall pre-
vent coil assembly from contacting the sheet
metal coil pan to minimize potential for galvanic
corrosion between coil and pan. All copper con-
struction shall provide protection in moderate
coastal environments.
50TFQ004-012
542J150,180