109
PERFORMANCE DATA
COOLING CAPACITIES
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leav-
ing indoor coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering indoor coil
3. SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x (edb 80).
542J150
Temp (F)
Air Ent
Outdoor
Coil
Air Entering Indoor Coil Cfm/BF
3750/0.04 4500/0.05 5000/0.05 5625/0.06 6250/0.07
Air Entering Indoor Coil Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
75
TC
167.0 154.0 140.0 171.0 158.0 144.0 173.0 159.0 146.0 171.0 162.0 148.0 173.0 161.0 151.0
SHC
79.6 100.0 120.0 85.0 108.0 131.0 87.5 114.0 138.0 94.5 120.0 146.0 97.7 127.0 150.0
kW
10.00 9.77 9.50 10.10 9.87 9.61 10.20 9.93 9.68 10.20 10.00 9.74 10.20 10.00 9.80
85
TC
160.0 148.0 133.0 164.0 151.0 137.0 167.0 154.0 140.0 168.0 155.0 143.0 166.0 157.0 146.0
SHC
77.6 98.9 118.0 82.0 107.0 129.0 86.1 113.0 136.0 89.6 118.0 142.0 95.3 125.0 146.0
kW
11.10 10.80 10.40 11.20 10.90 10.60 11.30 11.00 10.70 11.30 11.00 10.80 11.30 11.10 10.80
95
TC
155.0 141.0 127.0 157.0 144.0 131.0 160.0 146.0 133.0 161.0 149.0 137.0 163.0 149.0 140.0
SHC
76.1 96.3 115.0 80.3 105.0 126.0 84.4 110.0 132.0 86.5 117.0 137.0 91.7 121.0 140.0
kW
12.20 11.80 11.40 12.20 11.90 11.50 12.40 12.00 11.60 12.40 12.10 11.80 12.50 12.10 11.90
105
TC
147.0 133.0 120.0 150.0 137.0 124.0 152.0 138.0 127.0 153.0 140.0 131.0 154.0 141.0 134.0
SHC
73.6 93.3 112.0 78.5 102.0 123.0 81.6 108.0 127.0 85.1 114.0 131.0 88.6 120.0 134.0
kW
13.20 12.70 12.30 13.30 12.90 12.50 13.40 13.00 12.60 13.50 13.10 12.80 13.50 13.10 12.90
115
TC
140.0 126.0 112.0 141.0 129.0 118.0 144.0 130.0 121.0 144.0 131.0 125.0 146.0 133.0 128.0
SHC
71.4 90.3 109.0 75.1 99.1 117.0 78.9 104.0 121.0 81.9 110.0 125.0 87.0 117.0 128.0
kW
14.20 13.70 13.20 14.30 13.90 13.50 14.40 14.00 13.70 14.50 14.00 13.90 14.60 14.10 14.00
125
TC
131.0 118.0 105.0 134.0 120.0 111.0 135.0 122.0 115.0 137.0 123.0 118.0 136.0 124.0 121.0
SHC
68.1 87.6 105.0 73.5 96.4 111.0 75.7 102.0 115.0 80.7 108.0 118.0 83.4 113.0 121.0
kW
15.20 14.70 14.10 15.40 14.90 14.50 15.40 14.90 14.70 15.60 15.00 14.90 15.60 15.10 15.00
542J180
Temp (F)
Air Ent
Outdoor
Coil
Air Entering Indoor Coil Cfm/BF
4500/0.06 5250/0.08 6000/0.10 6750/0.10 7500/0.12
Air Entering Indoor Coil Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
75
TC
210.0 192.0 173.4 216.0 196.6 178.4 220.0 202.0 182.2 222.0 204.0 185.6 224.0 206.0 190.2
SHC
100.6 125.2 148.2 106.0 134.0 160.6 110.6 143.0 172.2 115.0 151.2 183.2 120.2 158.2 190.0
kW
13.58 13.12 12.66 13.76 13.28 12.84 13.88 13.44 12.98 13.96 13.52 13.10 14.02 13.60 13.26
85
TC
202.0 183.0 164.4 208.0 187.8 169.0 212.0 191.4 172.8 212.0 194.0 177.2 214.0 195.8 182.2
SHC
98.0 121.8 144.2 103.8 131.2 156.4 109.0 140.0 168.6 112.0 148.0 177.0 116.2 155.6 182.2
kW
14.86 14.32 13.78 15.08 14.52 13.98 15.22 14.66 14.14 15.26 14.78 14.30 15.34 14.86 14.50
95
TC
192.4 173.2 155.0 196.2 177.8 159.2 200.0 180.8 163.4 202.0 183.4 169.0 204.0 185.4 174.2
SHC
94.8 118.0 140.0 100.2 127.4 152.6 105.6 136.4 163.4 110.6 144.8 169.0 114.2 153.2 173.8
kW
16.16 15.52 14.88 16.32 15.72 15.10 16.48 15.88 15.30 16.62 16.00 15.54 16.64 16.12 15.76
105
TC
182.0 163.0 145.0 186.4 167.0 149.4 188.6 170.0 155.4 191.0 172.2 160.8 193.0 173.8 165.2
SHC
91.0 114.2 135.2 96.8 123.6 147.6 101.8 132.6 155.2 107.2 141.2 160.6 112.2 149.6 165.2
kW
17.36 16.64 15.92 17.58 16.86 16.16 17.70 17.04 16.48 17.84 17.18 16.74 17.94 17.28 16.96
115
TC
171.2 152.4 134.8 175.0 156.2 140.6 177.8 158.8 146.8 179.4 160.8 152.2 179.6 162.2 156.4
SHC
87.4 110.2 130.8 92.6 119.4 140.6 98.8 128.2 146.8 103.6 136.8 151.8 107.2 144.6 156.2
kW
18.54 17.72 16.90 18.76 17.94 17.24 18.94 18.12 17.60 19.02 18.28 17.90 19.04 18.38 18.16
125
TC
159.4 141.2 125.0 162.8 143.8 132.0 165.6 147.0 137.8 166.6 148.8 143.0 168.2 150.0 146.8
SHC
83.6 105.8 125.0 89.0 115.0 131.8 94.4 123.6 137.8 99.8 132.2 142.8 105.0 139.6 146.6
kW
19.64 18.74 17.88 19.86 19.00 18.34 20.00 19.12 18.72 20.20 19.28 19.00 20.20 19.40 19.28
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input
SHC
Gross Sensible Heat Capacity (1000 Btuh)
TC
Gross Total Capacity (1000 Btuh)
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79 78 77 76 75 under 75
81 82 83 84 85 over 85
Correction Factor
.05
1.04 2.07 3.11 4.14 5.18
Use formula
shown below.
.10
.98 1.96 2.94 3.92 4.90
.20
.87 1.74 2.62 3.49 4.36
.30
.76 1.53 2.29 3.05 3.82
50TFQ004-012
542J150,180