Bradford-White Corp BMT2H Boiler User Manual


 
BRADFORD WHITE CORP.
Page 4
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13 in. w.c. (3.2 kPa).
All installations must be made in accordance with:
1) In the U.S., the " National Fuel Gas Code "ANSI
Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having
Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC),
ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.
1.2 Model Identication
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
1-3 Model Series Designation
B M T 2 = Brute Deluxe
4 Usage
H = Hydronic
V = Volume Water
5-8 Size
0 2 0 0 = 199,900 BTU/h input
0 3 0 0 = 299,000 BTU/h input
0 4 0 0 = 399,900 BTU/h input
9 Fuel
N = Natural Gas
P = Propane
10 Altitude
A = 0-5000 feet
H = over 5000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-Off (standard)
K = Two-stage (optional)
13 Revision
1 = Revision Level 1
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. BMT2V)
C = Glass-lined cast iron / copper (std. BMT2H)
N = Glass-lined cast iron / cu-nickel (BMT2H)
P = Glass-lined cast iron / cu-nickel / brz trim (BMT2V)
2 = Glass-lined cast iron / copper, brz trim, HLW
5 = Glass-lined cast iron / cu-nickel / brz, HLW
15 Options Code
X = Standard unit
16 Pump Options
X = No Pump
1.3 Warranty
Bradford White's Brute Deluxe appliances are
covered by a limited warranty. The owner should
ll out the warranty registration card and return it to
Bradford White.
All warranty claims must be made to an
authorized Bradford White representative or directly
to the factory. Claims must include the serial number
and model (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figures 1A and 1B.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower oors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certied by CSA-
International for installation on combustible ooring;
in basements; in closets, utility rooms or alcoves.
Brute Deluxe Boilers or Water Heaters must never
be installed on carpeting. The location for the
appliance should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
control replacement, etc.). When vented vertically, the
Brute Deluxe must be located as close as practical to
a chimney or outside wall. If the vent terminal and/
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the
local area, both terminals should be installed at an
appropriate level above grade such that blockage of
the terminal from accumulated debris or precipitation
is prevented.