Power Supervision Base can be used as the last base on a loop
in four-wire systems to provide power supervision.
1. Release the mounting skirt from the mounting base. Use a
screwdriver at the location of the snap locks (refer to
Figure 2.1, item 12, page 4) to release the mounting skirt.
2. Run all system wiring (refer to Section 3.2 Wire the Bases
on page 10).
3. Mount the base using the two oblong mounting holes. Fits
4 in. square, octagon, AB, and single-gang back boxes.
4. Tighten the base to the mounting surface. Tighten only
until snug; not distorted.
i
NOTE! Follow NFPA 72 guidelines for mounting locations.
For commercial and industrial installations, 30 ft (9 m)
spacing between smoke detectors is recommended.
i
NOTE! Depending on local regulations, you can surface
mount the bases using anchors, mollies, or wing nuts, or
you can mount directly on back boxes.
i
NOTE! The electrical box must be large enough to
accommodate the number and size of conductors
specified by the National Electrical Code or any local
authorities having jurisdiction (AHJ).