5.3 Test the Alarm Loop
Checkthe voltage across the EOL resistor of each alarm loop to
verify wiring losses do not exceed control panel manufacturer’s
specifications.
5.4 Test any CO Sensors
Removing the detector head or resetting the detector’s power
places the detector in a special test mode for 15 minutes. If
over 35 ppm of CO is applied to the detector within this
15-minute period, the detector must alarm or it is defective.
5.5 Perform NFPA 72 Required Testing
Refer to Section 1.2 Required Maintenance and Testing on
page 2.
!
WARNING! The F220-PTHC detects carbon monoxide
(CO) as a component of a fire. Do not use the F220-PTHC
as a stand-alone CO detector.