30 Bosch Security Systems, Inc. | 9/11 | F01U245224-02
3.5 Arming and Disarming with Keyswitches
Arming Beeps and Flashes
The SIA standard requires that the control panel provide a means
to annunciate a change in arming state made from a Keyswitch.
The Alarm Bell output pulses on twice when a user disarms with a
remote device. The Alarm Bell output pulses on once when a user
arms with a remote device
3.6 Alarm Transmission Sequence – Alarm Abort
The SIA standard requires an Alarm Abort feature. The control
panel uses this feature to give end users an opportunity to
acknowledge an alarm event and abort the alarm transmission.
The following sections explain how this feature works.
3.6.1 Abort Window
The Abort Window is the time the end user has to acknowledge an
alarm and effectively “abort” the control panel’s alarm response.
The Abort Window is programmable.
The minimum duration is 15 sec.
The maximum duration is 45 sec.
The default is 30 sec.
In accordance with UL standards, the SIA standard
intends that the combined Entry Time and Abort
Window will not be programmed to exceed one
minute.
3.6.2 Passcode Acknowledges Alarm
When the control panel is sounding an alarm, enter [passcode] +
[ESC] to silence the alarm without disarming. Entering the first
digit of the passcode temporarily silences the alarm at the keypad.
If a valid passcode is not entered, the alarm begins sounding again
after a period of about 10 sec with no keypad activity.