Fig. 5.19 Wet mode and dry mode of the AMC2 4W relay outputs
For the protection of damage the relay keep in mind, that ...
the maximum switching current is 1,25A
the maximum switching voltage is 30V DC
ohm resistive load can be connected to the relay, only
inductive loads have to be short circuited using recovery
diodes - see: Figure 5.20. These diodes (BAX12A) are sup-
plied with every AMC2 4W package.
If you need higher voltage for special constructions you
can connect external relays to the outputs. Recommended,
depending on the power supply mode, are the relay types
of the company Wieland:
Flare move 12DC1W10A
Flare move 24DC1W16A
But you can also use products of manufacturer in your
country - take care that the values of the product are iden-
tical with the products listened above.
!
WARNING!
Keep in mind the following specifications.