Beckett 7505 Burner User Manual


 
Table 1 - Models and Cross Reference Guide
Beckett GeniSys
TM
Control Part No.
Lockout
Time
Valve-on
delay time
2
Motor-off
delay time
2
Replaces
Honeywell:
Replaces
Carlin:
7505A 0000
15 sec - - R7184A, R8184G
48245, 40200,
42230, 50200
1
7505B 1500 15 sec 15 sec - R7184B -
7505P 1515
15 sec 15 sec 15 sec
R7184P, R7184U
1
60200
1
7505P 1530
15 sec 15 sec 30 sec
R7184P, R7184U
1
60200
1
7505P 152M
15 sec 15 sec 2 min
R7184P, R7184U
1
60200
1
1 Beckett snap-on alarm module required for direct replacement of this control.
2 Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-
on programming display. Other factory set timings are available. Contact Beckett for alternate
timings.
Features
Thermostat / Operating (if applicable) and Limit Control Compatible
Welded Relay Protection
Limited Recycle
Limited Reset
3 Status Lights
Valve-On Delay / Motor-Off Delay (Field programmable with Beckett add-on Display)
15 Second Lockout Time
Interrupted or Intermittent Duty Ignition
Technician Pump Priming Mode
Disable Function
Cad Cell Resistance Indicator
Communication Ports (2)
Specications
Electrical Ratings
Inputs:
Voltage: 5 Vdc +4%
Current: 25 mA maximum display current
Environmental Ratings:
Storage Ambient Temperature: -22°F to +150°F (-35°C to +65°C)
Operating Ambient Temperature: -4°F to +150°F (-20°C to +65°C)
Moisture: 5 to 85% RH, non-condensing and non-crystalizing