Bard P1142A3 Air Conditioner User Manual


 
Manual 2100-324
Page 14
FAN BLADE SETTINGS
Shown in Figure 9 are the correct fan blade setting
dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.
FIGURE 9
FAN BLADE SETTING DIMENSIONS
SUCTION AND DISCHARGE TUBE
BRAZING
Compliant Scroll compressors have copper plated steel
suction and discharge tubes. These tubes are far more
rugged and less prone to leaks than copper tubes used on
other compressors. Due to different thermal properties of
steel and copper, brazing procedures may have to be
changed from those commonly used.
To disconnect: heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube can
be pulled out of suction fitting. (See Figure 10.)
To connect:
Recommended brazing materials: silfos with
minimum 5% silver or silver braze material with
flux.
Reinsert tube into fitting.
Heat tube uniformly in Area 1 moving slowly to
Area 2. When joint reaches brazing temperature,
apply brazing material. (See Figure 10.)
Heat joint uniformly around the circumference to
flow braze material completely around the joint.
Slowly move torch into Area 3 to draw braze
material into joint. (See Figure 10.)
Do not overheat joint.
ledoMAnoisnemiD
3A2411P
1A8411P
1A0601P
"57.1
"57.1
"57.1
TABLE 9
The above suction line temperatures are based upon
80°F dry bulb/67°F wet bulb (50% RH) temperature and
rated airflow across the evaporator during cooling cycle.
ledoM
detaR
wolfriA
FeergeD59
DO
erutarepmeT
FeergeD28
DO
erutarepmeT
3A2411P
1A8411P
1A0610P
0041
0551
0071
95-75
75-55
94-74
06-85
16-95
65-45
SERVICE AND TROUBLESHOOTING
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all
times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system which shortens equipment service life as well
as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure
that they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and
unrestricted airflow circulation is essential.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. Pressure tables can be found in Table 10 in this
manual covering all models on cooling cycle. It is
imperative to match the correct pressure table to the unit
by model number.
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit rating
plate. Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 9.