Bard CH3S1 Dehumidifier User Manual


 
Manual 2100-506D
Page 7 of 14
High Side Pressure:±5°
evacuated, and recharged to serial plate instructions.
Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V
SYSTEM REFRIGERANT PRESSURE CHART
Low Side pressure: ±2°
Table is based upon rated CFM (airflow) across the Evaporator
Coil. If there is any doubt as to the correct operating charge
being in the system, the charge should be removed, system
7961-679
50% RH 55% RH 60% RH
65% RH
70% RH 75% RH 80% RH
Low Side 96 97 98
100
102 104 106
Hi
g
h Side 248 253 258
261
265 269 273
Low Side 110 112 114
116
117 118 120
Hi
g
h Side 270 276 282
288
294 298 303
Low Side 115 119 123
127
132 136 140
Hi
g
h Side 297 306 315
324
333 342 351
Low Side 120 127 134
141
148 153 158
Hi
g
h Side 342 349 356
363
370 375 380
75° DB
80° DB
85° DB
Relative Humidity %Return Air
Temperature
Pressure
70° DB
TABLE 2
CHARGING PRESSURE LABEL