Bard 8403-060 Thermostat User Manual


 
997-060180-4d
3
PROGRAM MENU
SAVE
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
WEEKDAYS
WEEKENDS
COPY
SELECT OPTION
∇∆
PRE
VIOUS
EVERY DAY
SECURITY LOCKOUT
TEMP ADJUST ONLY
SELECT OPTION
∇∆
PREVIOUS
TOTAL KEYPAD LOCKOUT
SECURITY LOCKOUT
ENTER PIN NUMBER
0 0 0 0
CHANGE NUMBER
∇∆
PREVIOUS
INTERMITTENT FAN
NO HEAT OR COOL CALL
FAN OFF TIME
10
MINUTES
CHANGE SETTING
∇∆
PREVIOUS
EVERY DAY
ACTIVE HEAT COOL FAN
70 78 AUTO
IDLE
10:00P 62 82 AUTO
SAVE
PREVIOUS
6:00A
INTERMITTENT FAN
NO HEAT OR COOL CALL
FAN ON TIME
5
MINUTES
CHANGE SETTING
∇∆
PREVIOUS
the MODE to OFF, and then back to the operating mode,
typically AUTO.
4. If step 3 is not done within 10-minutes the display will
automatically return to the SERVICE NEEDED screen in RED.
II. PROGRAMMING YOUR CONTROLLER (programmable
models only)
PROGRAMMING A DAY OR A SERIES OF DAYS
After selecting the programming screen, you have the option of
programming everyday, weekdays, weekends, or individual days. Once
you’ve selected a certain day to program, a screen appears that allows
you to set the time, heat setting, cool setting, and fan operation for each
event.
1. From the Main Menu, scroll to MENU and press the center button
on the keypad.
2. Select PROGRAM
3. Select PROGRAMMABLE.
4. You can program each day differently
by going through each day and
personalizing them. Or, you can program
everyday the same by scrolling to
EVERYDAY. Or, you can program
the weekdays or weekends the same by
selecting the appropriate menu item.
5. To program everyday the same, select
EVERYDAY and then press the center
button .
6.
Using the right arrow button , highlight
the WAKE time, and change to desired
time by using the up and down arrow ▲▼
buttons. Move to the next entry by using
the right arrow button . To change the
HEAT set point, use the up and down arrows.
Continue this process until all settings are to your liking.
7. The FAN setting will only be used if the Fan is set to
PROGRAMMED. If the Events are set to 2 per day in the
Business mode, the fan will be ON and the Ventilation output
(A) will be ON when the time is in the OCCUPIED (Active) state. In
the Unoccupied (IDLE) state, the fan will run in the operating
mode set by the program.
8. To save these setting, scroll to SAVE, and press the center button .
COPYING A PROGRAM FROM ONE DAY TO ANOTHER
In the PROGRAM menu, there is an option to COPY. The option can
be used to copy the program from one day to another day. After
COPY is selected, the controller will prompt you for which day to
copy from. Next, it will prompt you for which day to copy the
program to. After these selections, it will then confirm what is being
copied to where. At this point you have the option of canceling the
copy process, by pressing
to return to the copy menu, or saving what you have b
y pressing
the center button . The SAVED screen will appear returning you to
the copy menu. Pressing will return you to the PROGRAM menu.
Pressing again will return you to the MAIN MENU.
SECURITY LOCKOUT
This controller has the option to set security
features to lockout everything but the adjustment
of the temperature or a total keypad lockout.
1. From the Main Menu, scroll to MENU and
press the center button on the keypad.
2. Select SECURITY LOCKOUT.
3. Select whether you want to lockout everything
but TEMP ADJUST ONLY or TOTAL
KEYPAD LOCKOUT.
4. Either selection will bring you to the Enter Pin
Number screen.
5. Using the up and down arrows ▲▼, select a
pin number to lock out the thermostat. The
right arrow moves you to the next pin digit.
6. Once you’ve entered the 4-digit pin number, press the center button
to save the pin. The screen will display LOCKED and return to the
main Screen.
7. Once you return to the Main Screen, in the upper left of the screen
will alternate between LOCKED and the date and time.
8. If you selected TEMP ADJUST ONLY, you will only be able to
adjust the set point temperature. Any other operation will require the
pin number to unlock the controller.
9. Once unlocked, you’ll have to set a pin number again to lockout the
thermostat again.
AUTO CHANGEOVER
With auto changeover, the controller automatically switches itself from
heating to cooling, or vise versa, based on the setpoints. When setting up
the controller you have to enter both a cooling setpoint and a heating
setpoint. The controller will also prevent the user from setting the cooling
setpoint lower than the heating setpoint. Mode is set to AUTO for this
operation to work.
MENU
SETTINGS AUTO CHANGEOVER
Auto Changeover Time - This setting sets the minimum off time before the
controller can change from one mode to another.
Default is 10 minutes. Range is from 5-120
minutes in 5 minute increments. Pressing the
Right and Left buttons together for 3 seconds will
over ride this delay for one cycle.
Auto or Manual Change – Default is AUTO. If MANUAL is chosen, you
will need to change from heating to cooling or
vise versa. When MANUAL is set, AUTO is
removed from the MODE screen as a choice.
INTERMITTENT FAN
MENU SETTINGS INTERMITTENT FAN
Temperature conditions can vary widely between the controller location
and extremities of the space the controller serves. This air stratification
problem can be especially pronounced during mild outdoor conditions
when long periods elapse between space conditioning demands from the
controller. This intermittent fan operation can also improve the
performance of air cleaning or special filtration systems that locate the
cleaning or filtration media at the return air side of the fan.
1. If the FAN hasn’t been on for an hour, the fan
will start cycling based on these times. Default is
OFF. The first screen is the amount of time you
want the fan to be energized. Ranges are OFF, or
5-20 minutes in 5 minute increments.
2. After entering this time and pressing the center
button , the next screen is the amount of time the
fan
is OFF. Ranges are 0 minutes, or 5-40
minutes in 5 minute increments.
3. After entering this time and pressing the center
button you will be returned to the Setting Menu
screen.
4. Fan ON and OFF cycles will continue until the
fan has been energized by a call for heating or cooling.
SERVICE INFORMATION
MENU
SETTINGS
SERVICE INFORMATION
These screens help an installer or contractor to have a good understanding
of what problems might be occurring before arriving for service. The
options are TEMPERATURE and INPUTS. The TEMPERATURE will
display the internal sensor temperature, the Room temperature and the
reading from the Outdoor thermistor. INPUTS displays the status of the
controller control lines. (W1/E, W2, Y1, Y2, G, O/B, A, Y0/D)
WARNING: Before installing controller, turn off all power to unit. There
may be more than one power disconnect. Electrical shock can cause personal
injury or death.