Bacharach 2072-0400 Air Conditioner User Manual


 
MAC2000 Operation
Total Flush ........Time spent flushing and number of times it was
performed
Recovered .........Total amount of refrigerant recovered
Charged ............Total amount of refrigerant charged
Added ................Total amount of refrigerant transferred from the
external virgin tank to the internal storage tank
Filter life left .....Weight of refrigerant that can be charged before
the Filter Dryer needs replaced
Pressing Next again displays the “Job history” screen, which
contains the history of each job performed. A technician can press the
UP and Down keys to scroll through the last 75 jobs.
Tips: Holding down the Up or Down key speeds up scrolling.
The total screen can be cleared by entering the Set-up mode and
selecting “Clear totals?
Job history can be cleared by entering the Set-up mode and selecting
Clear job history?
3.8 Internal Tank Manual Refill
When the MAC2000 remains turned ON during the day, the unit
automatically refills the internal tank with refrigerant from the
external source tank. An operator, however, can manually add
refrigerant as follows:
1. If not already done, plug the MAC2000 into a properly grounded
AC outlet; set the Power switch to ON; then wait until the unit
completes its self diagnostics. The screen will display “Select
mode” when ready.
2. Press the Next menu function key to display Menu 2. Then press
the Tank refill function key to begin the refill process.
Note: If the tank is already filled with 12 lbs or more of refrigerant,
then the message “Tank already full” appears.
3. Press the Start key to continue. The screen will then display “The
internal tank is now being refilled.” When the internal tank is
filled, the screen displays “Tank refill complete.
4. Press the Reset key to return to the Main menu.
Instruction 2072-0400 25