Aprilaire 65 Dehumidifier User Manual


 
INSTALLATION
MOUNT CONTROL
PULL APART
FRONT COVER
BACK
PLATE
RH SETTING
LABEL
H
H
R
C
FIGURE 2 – Disassemble Control
90-1667
H
H
R
C
BACK PLATE
ANCHOR
SCREW
MOUNTING HOLES
WIRE ACCESS OPENING
4-CONDUCTOR WIRE
FIGURE 3 – Mount Back Plate
90-1668
See Figures 2 & 3.
1. Remove front cover by pulling straight out.
2.Positionthebackplateonthewallandmarkthelocationsforthewireaccessholeandthe
mounting screws. NOTE:Themountingholescanalsobeusedtosecurethebackplatetoa
standard horizontally mounted junction box.
3.Formountingondrywall,drilltwo3/16”dia.mountingholesanda3/4”openingforthewires.
4. Insert the drywall anchors provided into the mounting holes flush with the wall surface.
5. Run 4-wire cable from the humidifier to the control location.
6.Securebackplateusingthetwo#8x1-1/2”screwsprovided.
7.Afterconnectingthewires,tuckexcesswireintothewallandfilltheopeningwithinsulating
material. Failure to seal the opening may result in inaccurate operation due to drafts.
WIRING
WIRING – Model 65 with Aprilaire Model 400, 500, 600, and 700 Series
Evaporative Humidifiers
The Model 65 control requires 24VAC. Drawing power from the HVAC system is the
recommended method for this installation. See Figures 4 & 5.
1. Disconnect power to the humidifier and HVAC system.
2. Connect the C and R terminals on the Model 65 to the HVAC or thermostat C and R terminals.
3. Connect Model 65 H terminals to the humidifier solenoid valve control circuit as shown.
4.Snapthefrontcoverontothebackplate.The4-pinterminalalignswiththeterminalblock
receptacleonthebackplate.
5. Proceed to SYSTEM CHECKOUT on page 9.
4
5