JANUARY 2008 UCCS STANDARDS 15950-3
flows, shall be by the Balancing Contractor. The Controls Contractor shall provide assis-
tance to the Balancing Contractor with control adjustments as required to obtain design
flows by:
1. Providing on-site instruction on the proper interfacing and operation of their
equipment
2. Providing the necessary software for use with the balancer's personal computer for
interfacing with their control equipment. Where proprietary equipment/gateways are
required, this equipment shall be provided for the Balancing Contractor's use.
F. Airflow stations are provided and installed by the Mechanical Contractor. The Controls
Contractor shall make all necessary connections to the control system.
1. Flow meters and other control devices furnished by other contractors shall have all
necessary connections to the control system made by the Controls Contractor.
1.02 SPECIAL CONDITIONS
A. The University uses only Delta Controls for all DDC applications.
The University prefers to use Setpoint for all Delta products. Can we put a fixed price agree-
ment with Setpoint for Delta products. Stating we have an agreed upon multiplier for pricing?
B. Currently, Setpoint is the only Delta provider in this area, providing a proximity benefit.
Setpoint is also the current provider for Delta control systems providing a knowledge benefit.
Other providers may bid on the Delta contol systems. Setpoint ??? Who else can install Delta?
Rocky Mountain Power and Controls, with UCCS pre-approval
Westover Controls.
These companies competitively bid against each other for the entire controls portion of the
project; including design, programming, component purchasing, installation, and startup.
The cost of any Delta equipment will be included in their price, along with the cost of all
other items for which the Controls Contractor is responsible.
In order to perform programming, the company shall have staff who have been certified by
Delta within the last 3 years.
1.03 SCOPE
A. Type of System: The automatic temperature control system shall be Direct Digital Control
(DDC/EMCS) with electric and pneumatic components as required.
B. All digital and analog control loops shall be microprocessor (DDC) controlled with
electronic final control elements, unless otherwise shown on the Drawings.****
C. All damper and valve actuators, including those for smoke/fire or smoke dampers, shall be
electric, unless specified otherwise. If field conditions appear to require another type of
actuator, the University HVAC Shop shall be consulted, through the Engineer, for review