A.O. Smith GWV - 200 Water Heater User Manual


 
www.aosmithinternational.com
Data subject to change INT/1108/GWV/02
Terms and conditions apply, please refer to our website.
Flue systems Burkay - Genesis
Installation options
Parallel
Diameter (mm) 150 150 200
Max. length not insulated (m) 8 8 8
Max. length not insulated with
condense drain (m) 20 20 20
Max. length insulated (m) 20 20 20
Max. bends 2 2 2
* Please contact A.O. Smith when installing a Burkay - Genesis in a B23 situation.
** When applying a condensation outlet, the distance between the condensation
outlet and the unit may not exceed 8 metres.
The maximum length also applies in B23 installations with
different supply and flue duct lengths.
Note: horizontal flue runs must be installed with a fall of at
least 5 mm per metre towards the water heater.
GWV 120
GWV 150
GWV 200
A Burkay – Genesis water heater should be installed according
category B23*, C13 or C33.
Flue systems Burkay - Genesis
Minimum space requirements
Minimal space for wall duct (mm)
V 605 605 1070
W 940 940 1485
X 1245 1245 1495
Y 1090 1090 1090
Minimal space for roof duct (mm)
V 1950 1950 2370
W 1340 1340 1375
X 2395 2395 2780
X ** 1445 1445 1830
Y 1560 1560 1945
Y ** 610 610 995
For the parts numbers of components and flue gas ducts, etc.
please refer to the “Maintenance and accessories” chapter.
GWV 120
GWV 150
GWV 200
2 x Ø150 2 x Ø150 2 x Ø200
** Distance without concentric pipe between appliance and roof duct.
C13
C33