8
FIGURE 6
d.) Splice field wiring into existing wiring using code
authorized method (wire nuts, etc.).
e.) Be certain that neutral and line connections are not
reversed when making these connections.
f.) Close panel on the side of control box, make sure that
access panel is secured shut.
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER
OPERATION AFTER SERVICING.
Do not plug in power cord until vent system is completely
installed. The Power Vent operates on 110-120 Vac, therefore
a grounded outlet must be within reach of the six (6) foot
flexible power cord supplied with the unit (see fig. 1). The
power cord supplied may be used only where local codes
permit. If local codes do not permit the use of a flexible power
supply cord:
a.) Make sure the unit is unplugged from wall outlet. Remove
screws and open panel on front of control box.
b.) Cut the flexible power cord, leaving enough to be able to
make connections, then remove the strain relief fitting
from box.
c.) Install suitable conduit fitting in side of enclosure and
then follow (d.) and (e.) below.