The UNI•COM meets NFPA 72 for Remote Station Protective Signaling Service and
central station Signaling Service reporting requirements for: (a) the type of signal (b)
condition and (c) location of the reporting premises.
Since higher priority events take precedence over lower priority events, the
UNI•COM will transmit higher priority events before sending the lower priority
events. Priorities are as follows:
Event Activations
1. General Alarm
2. Zone/Point Alarm #N
3. General Supervisory
4. Zone/Point Supervisory #N
5. General System Trouble
6. AC Power Loss
7. Zone/Point Trouble #N
8. Low Battery
9. Telco Primary Line Fault
10. Telco Secondary Line Fault
11. NAC Fault Code
12. Communication Trouble, Primary Number
13. Communication Trouble, Secondary Number
14. EIA-485 Communication Bus Trouble
15. Serviceman on Premises
16. Walktest Start
17. System Automatic Test Report
18. System Abnormal Automatic Test Report
19. Manual Activated Test Report
Event Restorals
20. General Restoral
21. Zone/Point Alarm #N Restoral
22. General Supervisory Restoral
23. Zone/Point Supervisory #N Restoral
24. General System Trouble Restoral
25. AC Power Loss Restoral
26. Zone/Point Trouble #N Restoral
27. Low Battery Restoral
28. Telco Primary Line Fault Restoral
29. Telco Secondary Line Fault Restoral
30. NAC Fault Code Restoral
31. Communication Trouble, Primary Number Restoral
32. Communication Trouble, Secondary Number Restoral
33. EIA-485 Communication Bus Trouble Restoral
34. Serviceman off Premises
35. Walktest End
Where #N represents the zone or device ID number.
Note: The Unimode 200 has a maximum capacity of 99 addressable smoke detectors
and 99 addressable modules. When the UNI•COM is programmed for point transmis-
sion, the reported range of addresses is 001 to 099 for detectors at addresses 01 to 99
and 101 to 199 for modules at addresses 01 to 99.
When using AIM modules with the Unimode II, the UNI•COM will report AIM devices
in up to 8 zones maximum.