ADT Security Services 400 Home Security System User Manual


 
Read Status Options 4. Read Status
Unimode 400 Operations PN 50709:A 10/20/97 19
Presignal Delay Figure 16 shows a typical format for displaying software zone F0 (Presignal Delay):
Figure 16 Presignal Delay Screen
DELAY=180 shows the programmed Presignal delay of 180 seconds.
PAS=Yes shows that Positive Alarm Sequence (PAS) operation is selected in the
program; PAS=No shows that PAS operation is not selected in the program.
Releasing Zones Figure 17 shows the typical format for displaying Releasing Zones R0-R9:
Figure 17 Releasing Zone Screen
Note: Refer to the
Unimode400 Programming
Manual for information on
Releasing Zones and the Soak
Timer.
DELAY=30 shows the programmed delay time, in seconds.
ABORT=ULI shows the abort function (ULI, IRI, NYC, or AHJ, if an abort switch
is mapped to this zone.
CROSS=Y indicates that cross zoning is used (requires two or more detectors
programmed to this zone in alarm to activate the zone).
SOAK specifies the Soak Timer (automatic shut off of device) value
(0000-9999seconds; 0000 = no Soak Timer).
Time Control Zones Figure 18 shows the typical format for displaying time control zones F5 and F6:
Figure 18 Time Control Screen
Note: Refer to the
Unimode400 Programming
Manual for information on
detector sensitivity settings.
The Time Control screen provides the following information:
ON=7:00 OFF=18:00 shows the programmed times—in 24-hour (military)
format—when zone F5 automatically turns on and off each day.
DAYS= MTWTF H shows the programmed days-of-week when the On/Off times
are effective. H is a holiday schedule defined by the program for zone F7.
You can also select zone F5 or F6 for detector day/night sensitivity. For example, you
can do the following:
1. List zone F5 in the CBE of an initiating device, such as a smoke detector.
2. Set the On time for F5 to 07:00 and the Off time for F5 to 19:00.
3. When zone F5 is active at 07:00, the control panel forces the detector sensitivity of
any initiating device listed for zone F5 to the least sensitive setting. When zone F5
goes off at 19:00, the detector sensitivity returns to it’s original setting.
OFFPRESIGNALFUNCT PRESIGNAL DELAY
DELAY=180 PAS=NO F00
OFF SOFTWARE ZONE RELEASE CONTROL
DELAY=30 ABORT=ULI CROSS=Y SOAK=000 R0
OFF TIME FUNCTION TIME CONTROL
ON=07:00 OFF=18:00 DAYS=MTWTF H FO5
Indicates zone F5
Holiday schedule defined
by zone F7
The ON time for devices
programmed for zone F5
The OFF time for devices
programmed for zone F5