78-8117-0985-2 Rev C 7
6.0 Install Termination
6.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting
with the loose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the
vinyl tape marker previously applied (Figure 7).
NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue
supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE UNWINDING
THE CORE.
The material being removed at this step is mixed polymersNOTE:
waste.and can be recycled with
Vinyl Tape Marker
Counter-Clockwise
Figure 7
6.2 Connect ground braid to system ground according to standard practice.
Semi-Con Insulation Shield
Ridge at End of Cable
Insulation Shield (Semi-Con)
Ridge at End
of High-K Tube
Correct Installation of Termination on Tape Shielded Cable
Cable
Insulation
Conductor
Vinyl Tape
Marker
Envioronmental
Top
Seal
Stress Controlling Compound
High-K Stress
Relief Tube