3M 7623-T-110 Air Conditioner User Manual


 
14 78-8113-5099-6 Rev E
Shield Wires
Constant Force Spring
Ground Braid
Solder Block
Ground Braid Leg
Trim
Cable
Wire
Shield
1st Scotch
®
Mastic Strip 2230
2nd Scotch
®
Mastic Strip 2230
Figure 21
13.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring
and exposed shield wires (Figure 22).
NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.
Semi-Con
Constant Force Spring
Two Half-Lapped Layers of Electrical Grade Vinyl Tape
Shield Wires
Vinyl Tape Marker
1-1/2" (38 mm)
Scotch
®
Mastic Strip 2230
Figure 22
14.0 Install Lug or Connector
Important Packaging Notice
In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed
with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the
termination. This shipping core can be recycled with other polypropylene waste.
14.1 Check to insure 3M
Cold Shrink QT -III Silicone Rubber Termination fits over the selected lug or connector. If
lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.0) and slide
termination on cable before installing lug or connector. DO NOT REMOVE CORE AT THIS TIME.
Clearance
Connector/Lug
Figure 23