A SERVICE OF

logo

036-21044-003-A-0304
Unitary Products 17
TABLE 7: COOLING CAPACITY 35.1 KW UNIT - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 29°C Temperature of Air on Condenser Coil 35°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30 28 27 25 23 22 20 30 28 27 25 23 22 20
1.42
22
43 11.2 24 22 19 16 14 - - 40 12.0 23 21 18 16 13 - -
19
39 10.8 30 28 25 22 20 17 15 36 11.6 29 26 24 21 19 16 14
17
37 10.5 35 33 30 28 25 23 20 34 11.2 34 32 30 27 25 22 20
14
36 10.6 36 34 31 29 26 24 21 32 11.4 32 32 30 27 25 22 20
1.65
22
44 11.4 26 23 20 17 14 - - 41 12.2 25 22 19 16 13 - -
19
40 11.0 33 30 27 24 21 18 15 37 11.7 31 28 25 22 19 16 13
17
37 10.6 36 35 32 29 26 23 21 34 11.4 34 34 31 28 25 23 20
14
36 10.7 36 35 34 31 28 25 22 33 11.5 33 33 31 28 26 23 20
1.89
22
44 11.6 28 25 22 18 15 - - 41 12.4 27 24 20 17 14 - -
19
40 11.2 35 32 28 25 22 18 15 37 11.9 34 30 27 23 20 16 13
17
37 10.8 37 37 34 31 28 24 21 35 11.5 35 35 33 30 26 23 20
14
37 10.9 37 37 36 32 29 25 22 33 11.7 33 33 33 30 26 23 20
2.12
22
45 11.7 31 27 23 19 15 - - 42 12.4 30 26 22 19 15 - -
19
41 11.3 38 34 30 26 22 19 15 38 12.0 36 33 29 25 21 18 14
17
38 10.9 38 38 37 33 29 25 21 35 11.6 35 35 34 31 27 23 19
14
37 11.0 37 37 37 33 29 25 21 34 11.7 34 34 34 30 26 22 18
2.36
22
46 11.7 33 29 24 20 16 - - 42 12.5 33 29 24 20 16 - -
19
41 11.4 41 36 32 28 23 19 15 38 12.1 38 36 32 27 23 19 14
17
39 11.0 39 39 39 34 30 26 21 36 11.7 36 36 36 31 27 23 18
14
38 11.1 38 38 38 34 29 25 20 34 11.8 34 34 34 30 25 21 16
Temperature of Air on Condenser Coil 41°C Temperature of Air on Condenser Coil 46°C
1.42
22
38 12.8 22 20 17 15 12 - - 36 13.5 21 18 16 13 11 - -
19
34 12.3 28 25 23 20 18 15 13 31 13.0 26 24 21 19 16 14 11
17
32 11.9 32 30 28 25 23 20 18 30 12.6 30 29 26 24 21 18 16
14
30 12.1 30 30 27 25 22 20 17 29 12.8 29 27 25 22 20 17 15
1.65
22
38 13.0 24 21 18 15 12 - - 36 13.7 23 20 17 14 11 - -
19
34 12.5 30 27 24 21 18 15 12 31 13.2 29 26 23 20 17 14 11
17
32 12.1 32 31 30 27 24 21 18 30 12.8 30 29 28 25 22 19 16
14
31 12.3 31 30 29 26 23 20 17 29 13.0 29 28 27 24 21 18 15
1.89
22
38 13.1 26 23 19 16 13 - - 36 13.9 25 22 18 15 11 - -
19
34 12.7 32 29 26 22 19 15 12 31 13.4 31 28 24 21 18 14 11
17
32 12.3 32 32 32 28 25 21 18 30 13.0 30 30 30 26 23 20 16
14
31 12.4 31 31 31 27 24 21 17 29 13.2 29 29 29 25 22 18 15
2.12
22
39 13.2 29 25 21 17 13 - - 36 14.0 27 24 20 16 12 - -
19
35 12.7 34 32 28 24 20 16 12 31 13.5 31 30 26 22 19 15 11
17
33 12.4 33 33 32 29 25 21 17 31 13.1 31 31 31 27 23 19 15
14
31 12.5 31 31 31 27 24 20 16 29 13.3 29 29 29 25 21 17 14
2.36
22
40 13.3 31 27 23 18 14 - - 37 14.1 30 25 21 17 12 - -
19
35 12.8 35 34 30 26 21 17 13 32 13.6 32 32 28 24 20 15 11
17
33 12.5 33 33 33 29 25 20 16 31 13.2 31 31 31 27 22 18 14
14
32 12.6 32 32 32 27 23 19 14 30 13.4 30 30 30 25 21 17 12
Temperature of Air on Condenser Coil 52°C
1.42
22
34 14.2 20 17 15 12 10 - -
19
28 13.7 25 23 20 18 15 12 10
17
28 13.3 28 27 24 22 19 17 14
14
27 13.5 27 25 22 20 17 15 12
1.65
22
33 14.5 22 19 16 13 10 - -
19
28 13.9 27 25 22 19 16 13 10
17
28 13.5 28 27 26 23 20 17 14
14
26 13.8 26 26 24 21 18 15 12
1.89
22
33 14.7 24 21 17 14 10 - -
19
27 14.2 27 27 23 20 16 13 10
17
27 13.8 27 27 27 25 21 18 15
14
26 14.0 26 26 26 23 19 16 12
2.12
22
34 14.8 26 22 18 14 10 - -
19
28 14.3 28 28 25 21 17 13 9
17
28 13.8 28 28 28 25 21 17 13
14
27 14.1 27 27 27 23 19 15 11
2.36
22
35 14.9 28 24 19 15 11 - -
19
29 14.4 29 29 27 22 18 13 9
17
29 13.9 29 29 29 25 20 16 12
14
28 14.2 28 28 28 23 19 15 10
1 These capacities are gross ratings. For net
capacity, deduct air blower motor. Refer to the
appropriate Blower Performance Table for the
kW of the supply air blower motor.
2 These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.