A SERVICE OF

logo

036-21484-001-B-0103
Unitary Products 11
TABLE 7: DJ 150 (12-1/2 TON) CAPACITY RATINGS
Size
(Tons)
Model
Cooling Capacity
ARI Ratings
*
CFM
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
Gas Heat Capacity Gas
Line
Size
(in. OD)
MBH EER IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency (%)
Temp.
Rise (°F)
150
(12-1/2)
Cooling
Only
144 10.8 11.2 3750 86
--- - --
Electric
Heat
18, 24, 36
54
-- - - -
Gas Heat - 180 144 80 10-40 3/4
Gas Heat - 240 192 80 25-55 3/4
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
Rated in accordance with ARI 270 standard.
See Table 11.
TABLE 8: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
187 252
460-3-60 432 504
575-3-60 540 630