Function Operation output specifications (in case of positive logic)
Positive
logic
Negative
logic
Over-torque detection
ON:The state that torque component is H, H set
value or larger continued more than H set value.
Braking resistor
overload pre-alarm
ON:A certain rate of braking resistor overload trip (QNT)
detection time is over.
OFF:The detection time is within a certain limit.
In emergency stop
ON:In emergency stop operation (G is indicated).
OFF:The detection time is within a certain limit.
In retry
ON:In retry operation (TVT[ is indicated).
OFF:No retry operation is performed.
Pattern operation
switching output
ON:In normal operation or pattern operation has finished.
OFF:In pattern operation.
PID deviation limit ON:PID deviation is in H or H set value.
Run/Stop
ON:Running frequency is output or DC injection breaking (FD)
is performed.
Serious failure
(OCA,
OCL, EF, phase failure,
etc.)
ON:Serious failure (QEC, QEN, GH, phase failure, abnormal
output, short-circuit) is detected.
OFF:Inverter has recovered from serious failure. (Serious
failure has been reset)
Light failure
(OL, OC1,
2, 3, OP)
ON:Light failure (QN, QE, QE, QE, QR) is detected.
OFF:Inverter has recovered from light failure. (Light failure has
been reset)
Commercial
power/inverter
switching output 1
Refer to Section 6.19.
Commercial
power/inverter
switching output 2
Refer to Section 6.19.
Cooling fan
ON
/
OFF
ON:Cooling fan is in operation.
OFF:Cooling fan is off operation.
In jogging operation (In
jog run)
ON:In jog run
OFF:In normal operation
Operation
panel/terminal board
operation switching
ON:In operation by terminal board.
OFF:In operation by operation panel.
Cumulative operation
time alarm
ON:Cumulative operation time is beyond the H set value.
OFF:Cumulative operation time is less than the H set
value.
PROFIBUS/DeviceNet/CC-
Link communication error
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
Forward/reverse
switching
OFF:In forward operation. ON:In reverse operation.
It output command status while operation is stopped.
(When command status is not active, It will be "OFF")
Ready for operation 1
ON:In operable status (exclude during deceleration stop) or
operation can be started with frequency command input as an
operation switching answer-back.
OFF:In inoperable status.
Ready for operation 2
ON:In operable status or operation can be started with ST and
RUN signals and frequency command input.
OFF:In inoperable status.
Brake release (BR) Output the braking signal according to the brake sequence.
In (pre-)alarm status
ON:More than one of alarm, pre-alarm, undervoltage, low
current over-torque, poor control power supply, PID deviation
limit, abnormal frequency setting or torque limit have occurred
or detected.
OFF:All the alarms above are canceled.
Forward speed limit
(torque control)
ON:Forward operation speed is H set value or over.
OFF:Forward operation speed is less than H set value.
Reverse speed limit
(torque control)
ON:Reverse operation speed is Hҏset value or over.
OFF:Reverse operation speed is less than H set value.
Inverter healthy output ON and OFF are alternately output at intervals of 1 second.
RS485 communication
error
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
Error code output 1
Output the error code in 6-bit.
Error code output 2
Error code output 3
Error code output 4
Error code output 5