E6581222
15
■ Block Write 1, 2
Select data, which is desired to be written in block communications, in Block Communication Write
Data 1 and 2 Parameters (, ). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
* When “No selection” is specified in the parameters, no data will be written even though write data is
specified.
■ Block Read 1 to 5
Select read data, which is desired to be read in block communications, in Block Communication
Read Data 1 and 5 Parameters (to). This parameter becomes effective when
the system is reset, such as when power is turned off. When the setting is completed, turn off and
then on the power.
* Output current (FE03), output voltage (FE05) and PID feedback value (FE22) will become hold data
during a trip. Otherwise, real-time data appears.
* “0000” will be returned as dummy data, if “0 (No selection)” is selected for the parameter and “read”
is specified.
No. Block Write Data For data details, see:
0 No selection
1 Command 1 (FA00) “8.1 Command by communication”
2 Command 2 (FA20) “8.1 Command by communication”
3 Frequency Command Value (FA01) “8.1 Command by communication”
4 Terminal Board Output Data (FA50)
“8.3 Control of input/put signals from com-
munication”
5 Communication Analog Output (FA51)
“8.3 Control of input/put signals from com-
munication”
No. Block Read Data For data details, see:
0 No selection
1 Status 1 (FD01) “8.2 Monitoring from communication”
2 Output Frequency (FD00) “8.2 Monitoring from communication”
3 Output Current (FE03) “9. Parameter data”
4 Output Voltage (FE05) “9. Parameter data”
5 Alarm Information (FC91) “8.2 Monitoring from communication”
6 PID Feedback Value (FE22) “9. Parameter data”
7 Input Terminal Board Monitoring (FD06)
“8.3 Control of input/put signals from
communication”
8 Output Terminal Board Monitoring (FD07)
“8.3 Control of input/put signals from
communication”
9 Analog Monitoring VIA (FE35)
“8.3 Control of input/put signals from
communication”
10 Analog Monitoring VIB (FE36)
“8.3 Control of input/put signals from
communication”