6.19.6 Output Voltage Adjustment
When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of
operation, the LCD screen displays the output voltage on the present output voltage adjust
screen:
OUTPUT VOLT. ADJUST
OUTPUT VOLTAGE.=###%
>F1:DATA SET MODE
> Δ/∇ :PREV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
OUTPUT VOLT. ADJUST
REFERENCE ADJUST: ##
> Δ/∇ :CHANGE DATA
>ENTER: ACCEPT CHANGE
The locations marked ## will show the numerical value of the allowable voltage adjustment
parameter values. Press the 'up' and 'down' arrow keys to adjust the setting from between
±5 volts. This will cause the unit's output voltage to adjust to within ±2% of its nominal
value.
If the inverter is not running, and the output voltage cannot be adjusted; the following
message will be displayed:
OUTPUT VOLT. ADJUST
ADJUST PROHIBITED
DATA CANNOT CHANGE
>Δ/∇:PRV/NEXT SCREEN
Pressing the F1 key will have no effect on this display screen
6.19.7 Equalize Charge Mode Select
Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option.
DAMAGE to the battery system may occur if this option is used improperly.
4200FA CT/XT User’s Manual 56