A SERVICE OF

logo

SEPARATED COMBUSTION BLOWER UNIT HEATERS
15
W
X
F
C
G
M
N
S
O
K
/
16"
9
5
CC
J
L = C + P (APPROX.)
DD
P
Q x V
R x T
/
8"
7
4
/
4"
3
FILTER RACK
(OPTIONAL)
BLOWER
ENCLOSURE
(OPTIONAL)
OVAL COLLAR FITS
6" ROUND PIPE FOR
MODELS BSH 280 & 340 ONLY
A
H
D (OPENING)
BB
E
AA
B
K
GAS SUPPLY
CONNECTION
2
7
/
8
"
FF
/16 "
9
5
/2"
1
4
/8"
1
3
COMBUSTION AIR
INLET COLLAR
(SIZES 130-225)
COMBUSTION AIR
INLET COLLAR
(SIZES 130 - 225)
3
3
/
8
"
3
1
/
8
"
EE
4" ROUND FOR
BSH 130 thru 225
MODELS ONLY
The minimum recommended
installation clearance from top and
rear of unit (motor) is six inches.
Clearance to sides is eighteen
inches, and clearance at bottom
should equal “C” dimension shown
in table for each model.
Dimensions (in inches) — BSH
Dimension BSH 130 BSH 150 BSH 170 BSH 225 BSH 280 BSH 340
A
23-1/2 25-5/8 25-5/8 25-5/8 33-5/8 40
B
35-1/2 40-1/2 40-1/2 40-1/2 40-1/2 40-1/2
C
22 25 25 25 25 25
D
21-1/16 23-3/16 23-3/16 26-3/16 31-3/16 37-1/2
E
20 24 24 24 24 24
F
12-1/2 14-1/2 14-1/2 14-1/2
G
1 2 2 2 1-5/8 1-5/8
H
19-7/8 22 22 25 30 36-3/8
AA
8 9 9 9 9 9
BB
7-1/2 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2
CC
1 1/8 1/8 1/8 1 3/8 1 3/8
DD
3-1/4 3-1/4 3-1/4 3-1/4 3-5/8 3-5/8
EE
32-9/16 36 36 36 36-1/16 36-1/16
FF
6-1/2 6-1/2 6-1/2 6-1/2 5-7/8 5-7/8
J (Round)
4 4 4 4 6 6
K
3/8-16 3/8-16 3/8-16 3/8-16 3/8-16 3/8-16
N
atural Gas Connections
1/2 1/2 1/2 1/2 3/4 3/4
W
5 5
X
16 16
M
47-3/4 52-3/8 52-3/8 52-3/8 52-3/8 58-1/2
N
21 24-1/2 24-1/2 24-1/2 17-15/16 22-1/16
O
7-1/4 8-1/2 8-1/2 8-1/2 8-1/2 8-1/2
P
30 34 34 34 36 36
Blower Q (Height)
21-3/8 25 25 25 25 25
Enclosure Inlet Duct/R (Height)
20 23-3/4 23-5/8 23-5/8 23-5/8 23-5/8
(Accessory) Filter Rack Width T
27-1/2 32-3/4 32-3/4 32-3/4 42-7/8 42-7/8
Width V
29 34 34 34 44-1/4 44-1/4
S (Ctr. to Ctr. of Blower Mtg. Holes
17-3/8 20-3/8 20-3/8 20-3/8 20-3/8 20-3/8
Motor Pulley Diameter
3 3 3 3 3 3
Standard Blower Pulley Diameter
13 13 13 13 9 9
Approx. Shipping Weight
240 322 322 344 436 510
On blower units L = C + P is distance from front of unit to back of blower enclosure and minimum of distance to wall.
Dimension from rear of unit burner box to center line of gas pipe connection is 6-23/32" for BSH 130 and 6-1/2" for all other models.
BSH 130 through BSH 225 – 4 holes. BSH 280 and BSH 340 – 6 holes.
Distance between mounting hole in unit casing and mounting hole on blower, except on 280 and 340, then distance from rear mounting hole in casing.
Motor pulley is adjustable.
At 65°F ambient and unit fired at full rated input. Max mounting height as measured from bottom of unit, and without deflector hoods.
Note:Ratings shown are for elevations up to 2,000 feet.For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea
level. (In Canada see Rating Plate.) Reduction of ratings requires use of high altitude kit.
Data listed is for standard 115-volt, 60-Hertz, single-phase motors. All single phase motors are totally enclosed and thermal overload protected.
P
erformance — BSH
Outlet Max. Mtg. Heat
CFM Velocity Air Height (Ft.) Throw (Ft.)
Btu/Hr @ 55°F @55°F Temp. @ 55°F @ 55°F Standard Motor Data
Input Btu/Hr Temp. Temp. CFM Rise Temp. Rise Temp. Rise
Model
Output Rise Rise Range Range
HP Amps RPM Type
BSH 130
130,000 106,600 1795 682 1161-1795 55-85 11 30 1/4 5.4 1725 SP
BSH 150
150,000 123,000 2071 596 1340-2071 55-85 10 25 1/2 7.8 1725 SP
BSH 170
170,000 139,400 2347 675 1519-2347 55085 11 30 1/2 7.8 1725 SP
BSH 225
225,000 182,250 3068 781 1985-3068 55-85 13 35 3/4 10.2 1725 SP
BSH 280
280,000 229,600 3865 852 2501-3865 55-85 14 40 1 13.2 1725 CP
BSH 340
340,000 275,400 4636 869 3000-4636 55-85 15 40 1 13.2 1725 CP
Note: Mounting heights and throws for BSH models, without ductwork or nozzles, and at a cfm yielding a 55°F
temperature rise are the same as those listed for equivalent size PSH units.
Heater Parts from ACF Greenhouses