d. Excessive airow or draft causing ame to leave
burner head.
e. Excessive back pressure causing ame to be
erratic.
3. Control locks out after Trial For Ignition (TFI).
a. No oil to burner.
b. Shorted electrodes.
c. Nozzle clogged.
d. Airow too high.
e. Ignitor module defective.
f. CAD cell defective.
g. Oil valve stuck open or closed.
Note: The Safety Monitoring Circuit (SMC) is
designed to provide lockout in the event of a
stuck or welded motor relay.
SECTION XII: REPAIR PARTS
All MegaSteam™ Boiler Repair Parts may be obtained through your local U.S. Boiler Co., Inc. Wholesale Distributor. Should
you require assistance in locating a Wholesale Distributor in your area, or have questions regarding the availability of U.S. Boiler
Co., Inc. products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
NOTICE
If ame is not established within 15 seconds
of oil valve actuation (known as Trial For
Ignition [TFI]) lockout will occur. Lockout is
indicated by a red LED solid-on located on the
oil primary control.
Latch-up will occur if the control locks-out
three (3) times during a call for heat. This
is indicated by steady-on red and amber
LED's.