TABLE 37 – PULLEY ADJUSTMENT
UNIT Motor/Drive C ombo
Motor Pulley turns open
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
04
3
Phase
Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770
High Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
05
3
Phase
Medium Static 1303 1265 1226 1188 1150 1112 1073 1035 997 958 920
High Static 1639 1596 1553 1510 1467 1424 1380 1337 1294 1251 1208
06
3
Phase
Medium Static 1466 1423 1380 1337 1294 1251 1207 1164 1121 1078 1035
High Static 1687 1649 1610 1572 1533 1495 1457 1418 1380 1341 1303
07
3
Phase
Standard Static 747 721 695 670 644 618 592 566 541 515 489
Medium Static 949 927 906 884 863 841 819 798 776 755 733
High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909
08
3
Phase
Standard Static 733 712 690 669 647 626 604 583 561 540 518
Medium Static 936 911 887 862 838 813 788 764 739 715 690
High Static 1084 1059 1035 1010 986 961 936 912 887 863 838
09
3
Phase
Standard Static 733 712 690 669 647 626 604 583 561 540 518
Medium Static 936 911 887 862 838 813 788 764 739 715 690
High Static 1084 1059 1035 1010 986 961 936 912 887 863 838
--- Factory settings