Zephyr AK8200S Fire Extinguisher User Manual


 
INSTALLATION
MOUNT HEIGHTS
DUCTING
(AK8000AS, AK8100S, AK8200S)
Min 24"-Max 32"
36"
Minimum mount height between range top to
hood bottom should be no less than 24".
Maximum mount height should be no higher
than 32".
It is important to install the hood at the
proper mounting height. Hoods mounted too
low could result in heat damage and re haz-
ard; while hoods mounted too high will be
hard to reach and will loose its performance
and eciency.
If available, also refer range manufacturer's
height clearance requirements and recom-
mended hood mounting height above range.
A minimum of 6" round or 3-1/4” x 10"rectangular
duct must be used to maintain maximum air ow
eciency for AK8000/AK8100 and 8” minimum
must be used for AK8200.
Always use rigid type metal ducts only.
Flexible ducts could restrict air ow by up to 50%.
Also use calculation (on right) to compute total
available duct run when using elbows, transitions
and caps.
ALWAYS, when possible, reduce the number or
transitions and turns. If long duct run is required,
increase duct size from 6" to 7”or 8". If a reducer
is used, install a long reducer instead of a pancake
reducer. Reduce duct size as far away from open-
ing as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
Minimum clearance of 24”hood above range
height.
Maximum clearance 32" hood above range
height.
Minimum Duct Size:
Round:
6" minimum for AK8000AS/AK8100S
8" minimum for AK8200S
Rectangular:
Requires an adapter. Readily available at most
hardware stores.
Duct Run Calculation:
Maximum run
AK8100 (6" or 3-1/4” x 10") AK8200 (8”)
Deduct:
each 90 Elbow used
each 45 elbow used
each 6" to 3/14 x 10"
transition used
each 3/14 x 10" to 6"
each 3/14 x 10" to 6"
transition used
Side Wall Cap w/ damper
Roof Cap
100 FT
15 FT
9FT
1FT
5FT
30 FT
30 FT
e.g.- 1 roof cap, 2x90 elbows, 1 45 elbow used:
=30' + 30' + 9' =69' used, 31' available for straight duct runs.
Page 1
AK8000