York Y32 Air Conditioner User Manual


 
246653-YTG-E-0108
68 Johnson Controls Unitary Products
TABLE 53: ELECTRICAL DATA 40 TON WITH POWER EXHAUST R22
VOLTAGE
COMPRESSORS
(EACH)
OD F
AN MOTORS
(EACH)
S
UPPLY BLOWER PWR EXH MOTOR
MCA
1
(AMPS)
M
AX
FUSE
2
/
B
REAKER
3
SIZE
QTY. RLA LRA MCC QTY FLA HP FLA HP FLA
208-3-60 4 37.2 239 58.0 4 4.5
10 30.8
7.5 24.2 231 250
10 30.8 238 250
15 46.2 255 300
15 46.2
7.5 24.2 249 250
10 30.8 255 300
15 46.2 271 300
20 59.4
7.5 24.2 265 300
10 30.8 272 300
15 46.2 287 300
25 74.8
7.5 24.2 285 350
10 30.8 291 350
15 46.2 307 350
230-3-60 4 37.2 239 58.0 4 4.5
10 28.0
7.5 22.0 225 250
10 28.0 231 250
15 42.0 247 250
15 42.0
7.5 22.0 241 250
10 28.0 247 250
15 42.0 261 300
20 54.0
7.5 22.0 256 300
10 28.0 262 300
15 42.0 276 300
25 68.0
7.5 22.0 273 300
10 28.0 279 300
15 42.0 293 350
460-3-60 4 17.2 125 27.0 4 2.2
10 14.0
7.5 11.0 107 110
10 14.0 110 125
15 21.0 118 125
15 21.0
7.5 11.0 115 125
10 14.0 118 125
15 21.0 125 125
20 27.0
7.5 11.0 122 125
10 14.0 125 150
15 21.0 132 150
25 34.0
7.5 11.0 131 150
10 14.0 134 150
15 21.0 141 150
575-3-60 4 12.4 80 19.3 4 1.7
10 11.0
7.5 9.0 80 90
10 11.0 82 90
15 17.0 89 100
15 17.0
7.5 9.0 87 100
10 11.0 89 100
15 17.0 95 110
20 22.0
7.5 9.0 93 110
10 11.0 95 110
15 17.0 101 110
25 27.0
7.5 9.0 99 125
10 11.0 101 125
15 17.0 107 125
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC