TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued)
MODEL
BHH
POWER
SUPPLY
COMPRESSOR
COND.
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
1
AMPS
MAX.
HACR
2
BREAKER
SIZE
RLA LRA
MODEL
NO.
KW
TOTAL
AMPS
036 575-3-60 4.7 32.0 0.4 1.5
2NH04501058
2NH04501558
10.0***
15.0***
9.6
14.4
19.8
25.8
20
30
20
20
042 575-3-60 5.4 34.0 0.4 1.5
2NH04501058
2NH04501558
10.0***
15.0***
9.6
14.4
20.7
26.7
25
30
25
30
048 575-3-60 5.1 37.2 0.6 1.6
2NH04501058
2NH04501558
2NH04502058
2NH04502558
10.0***
15.0***
20.0***
25.0***
9.6
14.4
19.2
24.1
20.6
26.7
32.7
38.7
25
30
35
40
25
30
35
40
060 575-3-60 7.0 50.0 0.6 2.8
2NH04501058
2NH04501558
2NP04502058
2NP04502558
10.0***
15.0***
20.0***
25.0***
9.6
14.4
19.2
24.1
24.2
30.2
36.3
42.3
25
35
40
45
25
35
40
45
1
= Dual element, time delay type. * = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.
2
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table on previous page for 460 volts.
over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table on previous page for 575 volts.