York R-410A Air Conditioner User Manual


 
251934-YTG-G-0708
28 Johnson Controls Unitary Products
115°F 125°F
6250
77 313.7 29.7 138.3 114.3 87.2 - - - 295.1 32.3 123.1 105.9 78.7 - - -
72 288.1 29.4 182.3 155.1 127.9 100.7 - - 270.2 32.0 174.1 146.9 119.6 92.3 - -
67 262.5 29.0 226.2 195.8 168.7 141.5 114.3 - 245.2 31.7 219.9 187.8 160.5 133.3 106.0 -
62 245.5 28.5 245.5 245.5 209.1 182.0 154.8 127.6 230.5 31.1 230.5 230.5 202.7 172.5 145.2 118.0
7500
77 319.2 29.9 153.9 124.6 95.3 - - - 298.4 32.5 144.8 115.6 86.4 - - -
72 293.2 29.5 198.5 169.1 139.8 110.5 - - 273.2 32.2 189.7 160.5 131.2 102.0 - -
67 267.1 29.2 243.0 213.7 184.3 155.0 125.7 - 247.9 31.8 234.6 205.4 176.1 146.9 117.6 -
62 249.9 28.6 249.9 249.9 228.6 199.2 169.9 140.6 233.1 31.2 233.1 233.1 219.2 189.9 160.7 131.4
57 246.1 28.7 246.1 246.1 241.6 212.3 183.0 153.6 230.3 31.4 230.3 230.3 229.0 199.8 170.5 141.3
8750
77 324.8 30.0 169.6 134.8 103.4 - - - 301.7 32.7 166.6 125.3 94.1 - - -
72 298.3 29.7 214.6 183.2 151.7 120.2 - - 276.2 32.3 205.3 174.1 142.9 111.7 - -
67 271.8 29.3 259.7 231.5 200.0 168.5 137.0 - 250.7 32.0 249.3 222.9 191.7 160.5 129.3 -
62 254.3 28.8 254.3 254.3 248.0 216.5 185.0 153.5 235.7 31.4 235.7 235.7 235.7 207.3 176.1 144.9
57 250.4 28.8 250.4 250.4 262.2 230.7 199.2 167.7 232.8 31.5 232.8 232.8 232.8 218.1 186.9 155.7
10000
77 330.4 30.2 185.2 145.1 111.5 - - - 305.0 32.8 188.4 134.9 101.7 - - -
72 303.4 29.8 230.8 197.2 163.5 129.9 - - 279.2 32.5 220.9 187.7 154.5 121.3 - -
67 276.5 29.5 276.5 249.3 215.6 182.0 148.4 - 253.4 32.1 253.4 240.5 207.3 174.1 140.9 -
62 258.6 28.9 258.6 258.6 267.4 233.8 200.1 166.5 238.2 31.6 238.2 238.2 238.2 224.8 191.6 158.4
57 254.7 29.0 254.7 254.7 282.7 249.0 215.4 181.8 235.4 31.7 235.4 235.4 235.4 235.4 203.3 170.1
11250
72 298.2 30.1 240.3 208.6 177.0 145.3 - - 270.6 32.7 229.1 198.2 167.2 136.3 - -
67 271.7 29.7 271.7 258.1 233.3 201.6 170.0 - 245.5 32.4 245.5 245.0 224.3 193.4 162.5 -
62 254.2 29.2 254.2 254.2 258.6 226.9 195.3 163.6 230.9 31.8 230.9 230.9 230.9 209.8 178.9 148.0
57 250.3 29.2 250.3 250.3 264.3 232.7 201.0 169.3 228.2 31.9 228.2 228.2 228.2 214.4 183.4 152.5
12500
72 293.0 30.3 249.8 220.1 190.4 160.7 - - 262.0 32.9 237.3 208.6 179.9 151.2 - -
67 267.0 30.0 267.0 267.0 251.0 221.3 191.6 - 237.7 32.6 237.7 237.7 237.7 212.7 184.0 -
62 249.8 29.4 249.8 249.8 249.8 220.1 190.4 160.7 223.6 32.0 223.6 223.6 223.6 194.9 166.2 137.5
57 246.0 29.4 246.0 246.0 246.0 216.3 186.6 156.9 221.0 32.1 221.0 221.0 221.0 192.3 163.6 134.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ300 (25 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65