York PV9 Furnace User Manual


 
036-21584-001 Rev. B (1004)
Unitary Products Group 3
NOTE: For high altitude conversion, an orifice change may also be required. See Form 035-14447-001 for application information.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
NOTES:
1. All filters must be high velocity cleanable type.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
HIGH ALTITUDE PRESSURE SWITCH APPLICATION
Models
High Altitude Pressure Switch Kit
4,500 Ft to 10,000 Ft.
PV9A12N040UP11 1PS0506
PV9B12N060UP11 1PS0501
PV9B12N080UP11 1PS0502
PV9C16N080UP11 1PS0503
PV9C20N100UP11 1PS0505
PV9D20N120UP11 1PS0503
ELECTRICAL AND PERFORMANCE DATA
Models
Input
High/Low
Output
High/Low
Nominal
Airflow
AFUE
Air Temp.
Rise
Max. Outlet
Air Temp.
Blower
Blower
Size
Total Unit
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
MBH MBH CFM % °F °F HP Amps In. Amps
PV9A12N040UP11 40/26 38/24 1200 94.0 35-65 165 1/2 7.7 11x8 9 20 14
PV9B12N060UP11 60/39 56/36 1200 93.2 40-70 170 1/2 7.7 11x8 9 20 14
PV9B12N080UP11 80/52 75/49 1200 92.5 45-75 175 1/2 7.7 11x8 9 20 14
PV9C16N080UP11 80/52 75/49 1600 92.8 45-75 175 3/4 9.6 11x10 12 20 14
PV9C20N100UP11 100/65 93/60 2000 92.8 45-75 175 1 12.8 11x11 14 20 12
PV9D20N120UP11 120/78 112/73 2000 93.2 40-70 170 1 12.8 11x11 14 20 12
FILTER SIZES
Models CFM Cabinet Size Side Return Filter in. (cm) Bottom Return Filter in. (cm)
PV9A12N040UP11 1200 A 16 x 25 14 x 25
PV9B12N060UP11 1200 B 16 x 25 16 x 25
PV9B12N080UP11 1200 B 16 x 25 16 x 25
PV9C16N080UP11 1600 C 16 x 25 20 x 25
PV9C20N100UP11 2000 C 16 x 25 20 x 25
PV9D20N120UP11 2000 D (2) 16 x 25 22 x 25