Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* Wire size and overcurrent protection must comply with the National Electric Code.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
C
19-1/4
1-1/4
1-1/4
5/8
5/8
23-5/8
D
2-1/4
23-1/4
20
B
BOTTOMIMAGE
SUPPLYEND
TOPIMAGE
RETURNEND
LEFTSIDE
RIGHTSIDE
22-3/4
7/8
7/8
13-7/8
HORIZONTALCONDENSATE
DRAINOPENING2”
JUNCTIONBOX
HOLE7/8”
GASPIPEENTRY1-1/2”
CONDENSATEDRAIN
HOLE7/8”
SIDEPIPINGHOLE3-3/8”
T-STATWIRING7/8”K.O.
HORIZONTALCONDENSATE
DRAINOPENING1-3/4”
22-1/4
25-3/8
26-1/2
27-1/8
29
22-3/4
21-5/8
18-1/2
11-3/4
7-1/2
2-1/4
T-STATWIRING7/8”K.O.
HORIZONTALCONDENSATE
DRAINOPENING1-3/4”
HORIZONTAL
CONDENSATE
DRAINOPENING1-3/4”
JUNCTIONBOX
HOLE7/8”
GASPIPE
ENTRY1-1/2”
CONDENSATEDRAIN
HOLE7/8”
29
22-3/4
21-1/4
18-1/2
9-1/8
8-1/2
30-1/8
23-11/16
E
FRONT
A
40
CABINET AND DUCT DIMENSIONS
Models
CFM
CABINET
SIZE
CABINET DIMENSION
A (IN.) B (IN.) C (IN.) D (IN.) E (IN.)
PT9B12N060DH11 1200 B 17-1/2 16-1/4 15 1-3/4 2-3/8
PT9B12N080DH11 1200 B 17-1/2 16-1/4 15 1-3/4 2-3/8
PT9C16N080DH11 1600 C 21 19-3/4 18-1/2 2-1/8 2-3/4
PT9C20N100DH11 2000 C 21 19-3/4 18-1/2 2-1/8 2-3/4
PT9D20N120DH11 2000 D 24-1/2 23-1/4 22 2-1/2 3
ELECTRICAL AND PERFORMANCE DATA
Models
Input
(High/Low)
Output
(High/Low)
Nominal
Airflow
Cabinet
Width
Total Unit AFUE
Air Temp.
Rise
MBH MBH CFM In. Amps % °F
PT9B12N060DH11 60 / 39 56 / 36 1200 17-1/2 9 92 35 - 65
PT9B12N080DH11 80 / 52 75 / 49 1200 17-1/2 9 92 35 - 65
PT9C16N080DH11 80 / 52 75 / 49 1600 21 12 92 35 - 65
PT9C20N100DH11 100 / 65 93 / 61 2000 21 14 92 35 - 65
PT9D20N120DH11 120 / 78 112 / 74 2000 24-1/2 14 92 35 - 65
Models
Input
(High/Low)
Max. Outlet
Air Temp.
Blower
Blower
Size
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
Operating
Weight
MBH °F HP Amps In. Lbs.
PT9B12N060DH11 60 / 39 165 1/2 7.0 11 x 8 20 14 136
PT9B12N080DH11 80 / 52 165 1/2 7.0 11 x 8 20 14 143
PT9C16N080DH11 80 / 52 165 3/4 10.2 11 x 10 20 14 159
PT9C20N100DH11 100 / 65 165 1 12.7 11 x 11 20 12 164
PT9D20N120DH11 120 / 78 165 1 12.7 11 x 11 20 12 182